3 Communications Data for CompoWay/F
3 - 4
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
*1
The parameter for the currently selected PID set will be accessed. For setup area 1, however, the currently
selected PID set is fixed at PID1.
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C1 (81)
0000
Operation/Adjustm
ent Protect
H'00000000 (0) to H'00000005 (5)
0: No control
1: Operation level (PV displayed, PV/SP allowed,
others allowed), program level allowed,
adjustment level allowed, PID setting level
prohibited
2: Operation level (PV displayed, PV/SP allowed,
others allowed), program level allowed,
adjustment level prohibited, PID setting level
prohibited
3: Operation level (PV displayed, PV/SP allowed,
others allowed), program level prohibited,
adjustment level prohibited, PID setting level
prohibited
4: Operation level (PV displayed, PV/SP allowed,
others prohibited), program level prohibited,
adjustment level prohibited, PID setting level
prohibited
5: Operation level (PV displayed, PV/SP displayed,
others prohibited), program level prohibited,
adjustment level prohibited, PID setting level
prohibited
Protect
C1 (81)
0001
Initial
Setting/Communic
ations Protect
H'00000000 (0): Move to initial
setting/communications setting
level is allowed. (Move to advanced
function setting level is displayed.)
H'00000001 (1): Move to initial
setting/communications setting
level is allowed. (Move to advanced
function setting level is not
displayed.)
H'00000002 (2): Move to initial
setting/communications setting
level is prohibited.
C1 (81)
0002
Setting Change
Protect
H'00000000 (0): OFF (Changing of setup on
Controller display is allowed.)
H'00000001 (1): ON (Changing of setup on
Controller display is prohibited.)
C1 (81)
000D
Heater Burnout
Detection 1
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
C1 (81)
0012
Process Value
Input Shift
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
0013
PV Slope
Coefficient
H'00000001 to H'0000270F (0.001 to 9.999)
C1 (81)
0015
Proportional
Band
*1
H'0000001 to H'0000270F (0.1 to 999.9)