![Omron E5CC-T Communications Manual Download Page 103](http://html1.mh-extra.com/html/omron/e5cc-t/e5cc-t_communications-manual_742604103.webp)
5 - 9
5 Communications Data for Modbus
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
5
-1 V
ariab
le A
re
a (Setting
Rang
e) List
5
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byte
mode
0D32
2D19
Minimum Output ON/OFF
Band
H'00000000 to H'000001F4 (0.0 to 50.0)
Advanced
function
setting
0D34
2D1A
Program Time Unit
H'00000000 (0): Hours, minutes
H'00000001 (1): Minutes, seconds
Initial setting
0D36
2D1B
Step Time/Rate of Rise
Programming
H'00000000 (0): Step time programming
H'00000001 (1): Rate of rise programming
0D38
2D1C
Time Unit of Ramp Rate
H'00000000 (0): Minutes
H'00000001 (1): Hours
0D3A
2D1D
PV Start
H'00000000 (0): SP start
H'00000001 (1): PV start
0D3C
2D1E
Reset Operation
H'00000000 (0): Stop control
H'00000001 (1): Fixed SP operation
0E00
2E00
Transfer Output Type
H'00000000 (0): OFF
H'00000001 (1): Present SP
H'00000002 (2): PV
H'00000003 (3): MV (heating)
H'00000004 (4): MV (cooling)
H'00000005 (5): Valve opening (*Only for Position-proportional
Models.)
0E02
2E01
Transfer Output Signal
H'00000000 (0): 4 to 20 mA
H'00000001 (1): 1 to 5 V
0E0C
2E06
Control Output 1 Assign-
ment
Control output 1 is a relay output or voltage output (for driving SSR):
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Heater alarm
H'00000008 (8): HB alarm
H'00000009 (9): HS alarm
H'0000000A (10): Input error
H'0000000B (11): Program end output*
H'0000000C (12): Stage output
H'0000000D (13): RUN output
H'0000000E (14): Time signal 1 output
H'0000000F (15): Time signal 2 output
H'00000010 (16): Integrated alarm
H'00000011 (17): Work bit 1
H'00000012 (18): Work bit 2
H'00000013 (19): Work bit 3
H'00000014 (20): Work bit 4
H'00000015 (21): Work bit 5
H'00000016 (22): Work bit 6
H'00000017 (23): Work bit 7
H'00000018 (24): Work bit 8
When control output 1 is a linear current output:
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
Advanced
function
setting
0E0E
2E07
Control Output 2 Assign-
ment
Control output 2 is a relay output or voltage output (for driving SSR):
H'00000000 to H'0000018 (0 to 24)
Note: Same as for the Control Output 1 Assignment parameter.
When control output 2 is a linear current output:
H'00000000 to H'00000002 (0 to 2)
Note: Same as for the Control Output 1 Assignment parameter.