6 Programless Communications
6 - 22
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
Programless communications start operating after the power supply is turned ON or after the E5
@
C-T
is reset. They stop operating when the initial setting level is entered.
The following table gives the operation command codes that can be set.
For details on operation commands, refer to
You can check the operation of programless communications in the Communications Status in the
upload area.
The value of the Communications Status changes between 0 and 1 each time the upload area is
updated.
The E5
@
C-T normally writes the set values to non-volatile memory (i.e., in Backup Mode). If you fre-
quently change set values with programless communications, use an operation command to change to
RAM Write Mode.
6-3-3
Range of Operation for Programless Communications
Levels
Programless communications
Operation level, program setting level, adjustment level, PID
setting level, manual control level, monitor/setting item level,
and protect level
Setting area 0
Operates
Initial setting level, communications setting level, advanced
function setting level, and calibration level
Setting area 1
Stops
6-3-4
Operation Command Codes
Operation command
Operation command code
Switch
RUN/RESET
0100
RUN
0101
RESET
AT Execute/Cancel
030E
All PID 40% AT Execute
030F
All PID 100% AT Execute
0300
AT Cancel
0301
100% AT Execute
0302
40% AT Execute
Write Mode
0400
Backup Mode
0401
RAM Write Mode
Save RAM Data
0500
Save RAM Data
Software Reset
0600
Software Reset
Auto/Manual
0900
Automatic Mode
0901
Manual Mode
Alarm Latch Cancel
0C00
Alarm 1 Latch Cancel
0C01
Alarm 2 Latch Cancel
0C02
Alarm 3 Latch Cancel
0C03
Heater Burnout Latch Cancel
0C04
HS Alarm Latch Cancel
0C05
Alarm 4 Latch Cancel
0C0F
All Latch Cancel
SP Mode
0D00
Program SP Mode
0D01
Fixed SP Mode
Invert Direct/Reverse
Operation
0E00
Do Not Invert
0E01 Invert
Hold
1300
Hold cleared.
1301
Hold
Advance
1400
6-3-5
Confirming Operation of Programless Communications
6-3-6
Write Mode