5 Communications Data for Modbus
5 - 8
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byte
mode
0C00
2C00
Input Type
H'00000000 (0):
Pt (
−
200 to 850
°
C/
−
300 to 1500°F)
H'00000001 (1):
Pt (
−
199.9 to 500.0
°
C/
−
199.9 to 900.0°F)
H'00000002 (2):
Pt (0.0 to 100.0
°
C/0.0 to 210.0°F)
H'00000003 (3):
JPt (
−
199.9 to 500.0
°
C/
−
199.9 to 900.0°F)
H'00000004 (4):
JPt (0.0 to 100.0
°
C/0.0 to 210.0°F)
H'00000005 (5):
K (
−
200 to 1300
°
C/
−
300 to 2300°F)
H'00000006 (6):
K (
−
20.0 to 500.0
°
C/0.0 to 900.0°F)
H'00000007 (7):
J (
−
100 to 850
°
C/
−
100 to 1500°F)
H'00000008 (8):
J (
−
20.0 to 400.0
°
C/0.0 to 750.0°F)
H'00000009 (9):
T (
−
200 to 400
°
C/
−
300 to 700°F)
H'0000000A (10): T (
−
199.9 to 400.0
°
C/
−
199.9 to 700.0°F)
H'0000000B (11): E (
−
200 to 600
°
C/
−
300 to 1100°F)
H'0000000C (12): L (
−
100 to 850
°
C/
−
100 to 1500°F)
H'0000000D (13): U (
−
200 to 400
°
C/
−
300 to 700°F)
H'0000000E (14): U (
−
199.9 to 400.0
°
C/
−
199.9 to 700.0°F)
H'0000000F (15): N (
−
200 to 1300
°
C/
−
300 to 2300°F)
H'00000010 (16): R (0 to 1700
°
C/0 to 3000°F)
H'00000011 (17): S (0 to 1700
°
C/0 to 3000°F)
H'00000012 (18): B (100 to 1800
°
C/300 to 3200°F)
H'00000013 (19): W (0 to 2,300
°
C/0 to 3,200
°
F)
H'00000014 (20): PLII (0 to 1,300
°
C/0 to 2,300
°
F)
H'00000015 (21): Infrared temperature sensor (K 140
°
F/60
°
C)
H'00000016 (22): Infrared temperature sensor (K 240
°
F/120
°
C)
H'00000017 (23): Infrared temperature sensor (K 280
°
F/140
°
C)
H'00000018 (24): Infrared temperature sensor (K 440
°
F/220
°
C)
H'00000019 (25):
4 to 20 mA
H'0000001A (26):
0 to 20 mA
H'0000001B (27):
1 to 5 V
H'0000001C (28):
0 to 5 V
H'0000001D (29):
0 to 10 V
Initial setting
0C02
2C01
Temperature Unit
H'00000000 (0): °C
H'00000001 (1): °F
0C12
2C09
Scaling Lower Limit
H’FFFFF831 to scaling upper limit
−
1
(
−
1999 to scaling upper limit
−
1)
0C16
2C0B
Scaling Upper Limit
Scaling lower limit + 1 to H'0000270F
(Scaling lower limit + 1 to 9999)
0C18
2C0C
Decimal Point
H'00000000 to 00000003 (0 to 3)
0C22
2C11
Burnout Method
H'00000000 (0): Upscale
H'00000001 (1): Downscale
Initial setting
0D06
2D03
Control Output 1 Signal
H'00000000 (0): 4 to 20 mA
H'00000001 (1): 0 to 20 mA
0D08
2D04
Control Output 2 Signal
H'00000000 (0): 4 to 20 mA
H'00000001 (1): 0 to 20 mA
0D1E
2D0F
SP Upper Limit
The range of values (without decimal point) is as follows:
Temperature input: SP lower limit + 1 to Input range upper limit
Analog input: SP lower limit + 1 to Scaling upper limit
0D20
2D10
SP Lower Limit
The range of values (without decimal point) is as follows:
Temperature input: Input range lower limit to SP upper limit
−
1
Analog input: Scaling lower limit to SP upper limit
−
1
0D22
2D11
Standard or Heat-
ing/Cooling
H'00000000 (0): Standard
H'00000001 (1): Heating and cooling
0D24
2D12
Direct/Reverse Operation
H'00000000 (0): Reverse operation
H'00000001 (1): Direct operation
0D26
2D13
Close/Floating
H'00000000 (0): Floating
H'00000001 (1): Close
0D28
2D14
PID ON/OFF
H'00000000 (0): ON/OFF
H'00000001 (1): 2 PID control
Summary of Contents for E5CC-T