6 - 49
6 Programless Communications
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
6-6 C
onn
ecti
ng to MEL
S
EC
Q-series PLC
s
6
6-6-5 Che
c
king Oper
ation
With the default settings, the following parameters are set for the upload areas.
Check the values in the upload areas to see if they are the same as those that are given in
the following table. (It is not necessary to check address for which “---” is given in the Value
column.)
*
If the default settings are used and a sensor is not connected, the PV display on the E5CC-T will show an input
error (
s.err
) and the process value in the upload area will be 1320 (528 hex).
Changing E5CC-T Settings
(1) We will check the area that is used to change E5CC-T set values.
The area that is used to change the set value is called the download area.
D25 to D69 is the download area for the No. 0 Controller (E5CC-T), D95 to D139 is the
download area for the No. 1 Controller, and D165 to D209 is the download area for the No.
2 Controller.
No.0
No.1
No.2
Parameter
Value
D0000
D0070
D0140
Response Flag (fixed)
0
D0001
D0071
D0141
Communications Status (fixed)
Alternates between 0
and 1.
D0002
D0072
D0142
Communications Monitor
---
D0003
D0073
D0143
Status (Upper Word)
---
D0004
D0074
D0144
Status (Lower Word)
---
D0005
D0075
D0145
Status 2 (Upper Word)
---
D0006
D0076
D0146
Decimal Point Monitor
---
D0007
D0077
D0147
Process Value
Process Value *
D0008
D0078
D0148
Present SP
---
D0009
D0079
D0149
Internal Set Point
---
D0010
D0080
D0150
Heater Current 1 Value Monitor
---
D0011
D0081
D0151
PID Set No. Monitor
---
D0012
D0082
D0152
Program No. Monitor
---
D0013
D0083
D0153
Segment No. Monitor
---
D0014
D0084
D0154
Remaining Standby Time Monitor
---
D0015
D0085
D0155
Elapsed Program Time Monitor
---
D0016
D0086
D0156
Remaining Program Time Monitor
---
D0017
D0087
D0157
Elapsed Segment Time Monitor
---
D0018
D0088
D0158
Remaining Segment Time Monitor
---
D0019
D0089
D0159
Program Execution Repetitions Monitor
---
· · ·
· · ·
· · ·
· · ·
· · ·
D0024
D0094
D0164
Not used.
---