![Omron E5CC-T Communications Manual Download Page 125](http://html1.mh-extra.com/html/omron/e5cc-t/e5cc-t_communications-manual_742604125.webp)
6 - 9
6 Programless Communications
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
6-2 E5
@
C-
T C
ont
ro
lle
r Set
u
p
6
6-2-5 Are
as an
d First Address of Link
ed Data
Communications Setting Level
Display condition: The Protocol Setting parameter must be set to
fins
or
mcp4
.
Note: 1 The First Address Upper Word and First Address Lower Word parameters together specify the first
address.
Example: If the first address is 123456, set the First Address Upper Word parameter to 12 and the First
Address Lower Word parameter to 3456.
2 Set the same first address in all of the E5
@
C-T Controllers (e.g., set the same value as the value that is
set for the E5
@
C-T with communications unit number 0).
Address
Data in PLC memory
E5
@
C-T
Each E5
@
C-T
Controller is
allocated 70
words
XXXX
Response Flag
←
Communications Unit Number 0
+1
Communications Status
+2
Monitor Value 1
· · ·
+25
Request Flag
→
+26
Operation Command Code
+27
Set Value 1
· · ·
+70
Response Flag
←
No.1
+71
Communications Status
· · ·
· · ·
Parameter name
Displayed characters
Setting range
Default
Area
area
0:
DM (D data registers)
1:
EM0 (W link registers)
2:
EM1 (R file registers)
3:
EM2 (ZR file registers)
4:
EM3
5:
EM4
6:
EM5
7:
EM6
8:
EM7
9:
EM8
10:
EM9
11:
EMA
12:
EMB
13:
EMC
14:
EMD
15:
EME
16:
EMF
17:
EM10
18:
EM11
19:
EM12
20:
EM13
21:
EM14
22:
EM15
23:
EM16
24:
EM17
25:
EM18
Information in parentheses is applicable when the
Protocol Setting parameter is set to
mcp4
. Also, all set
values of 4 and higher specify D data registers.
0
First Address Upper Word
adrh
0 to 99
0
First Address Lower Word
adrl
0 to 9999
0
Summary of Contents for E5CC-T