![Omron E5CC-T Communications Manual Download Page 127](http://html1.mh-extra.com/html/omron/e5cc-t/e5cc-t_communications-manual_742604127.webp)
6 - 11
6 Programless Communications
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
6-2 E5
@
C-
T C
ont
ro
lle
r Set
u
p
6
6-2-8 Upload Settings and D
o
wnlo
ad Settin
gs
There are 23 upload settings and 43 download settings.
Communications Setting Level
Display condition: The Protocol Setting parameter must be set to
fins
or
mcp4
.
6-2-8
Upload Settings and Download Settings
Parameter name
Displayed
characters
Setting
range
Default
Upload Setting 1
up 1
0 to 179
1
Communications Monitor
Upload Setting 2
up 2
2
Status (Upper Word)
Upload Setting 3
up 3
3
Status (Lower Word)
Upload Setting 4
up 4
4
Status 2 (Upper Word)
Upload Setting 5
up 5
6
Decimal Point Monitor
Upload Setting 6
up 6
7
Process Value
Upload Setting 7
up 7
8
Present SP
Upload Setting 8
up 8
9
Heater Current 1 Value Monitor
Upload Setting 9
up 9
13
MV Monitor (Heating)
Upload Setting 10
up10
16
PID Set No. Monitor
Upload Setting 11
up11
17
Program No. Monitor
Upload Setting 12
up12
18
Segment No. Monitor
Upload Setting 13
up13
19
Remaining Standby Time Monitor
Upload Setting 14
up14
20
Elapsed Program Time Monitor
Upload Setting 15
up15
21
Remaining Program Time Monitor
Upload Setting 16
up16
22
Elapsed Segment Time Monitor
Upload Setting 17
up17
23
Remaining Segment Time Monitor
Upload Setting 18
up18
24
Program Execution Repetitions Monitor
Upload Setting 19
up19
0
Nothing assigned.
Upload Setting 20
up20
0
Nothing assigned.
Upload Setting 21
up21
0
Nothing assigned.
Upload Setting 22
up22
0
Nothing assigned.
Upload Setting 23
up23
0
Nothing assigned.
Download Setting 1
dn 1
30 to 179
32
Fixed SP
Download Setting 2
dn 2
42
PID 1 Proportional Band
Download Setting 3
dn 3
43
PID 1 Integral Time
Download Setting 4
dn 4
44
PID 1 Derivative Time
Download Setting 5
dn 5
78
Program 0 Alarm Value 1
Download Setting 6
dn 6
79
Program 0 Alarm Upper Limit 1
Download Setting 7
dn 7
80
Program 0 Alarm Lower Limit 1
Download Setting 8
dn 8
81
Program 0 Alarm Value 2
Download Setting 9
dn 9
82
Program 0 Alarm Upper Limit 2
Download Setting 10
dn10
83
Program 0 Alarm Lower Limit 2
Download Setting 11
dn11
36
Heater Burnout Detection 1
Download Setting 12
dn12
40
Process Value Input Shift
Download Setting 13
dn13
33
Wait Band
Download Setting 14
dn14
34
Standby Time
Download Setting 15
dn15
35
Program SP Shift Value
Summary of Contents for E5CC-T