5 - 15
5 Communications Data for Modbus
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
5
-1 V
ariab
le A
re
a (Setting
Rang
e) List
5
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byte
mode
1300
3300
Startup Operation
H'00000000 (0): Continue control at final SP
H'00000001 (1): RESET
H'00000002 (2): RUN
H'00000003 (3): Manual
*1
Initial setting
1302
3301
SP Tracking
H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
function
setting
1304
3302
PID Set Automatic
Selection Data
H'00000000 (0): PV
H'00000001 (1): DV
H'00000002 (2): SP
1306
3303
PID Set Automatic
Selection Hysteresis
H'0000000A to H'0000270F (0.10 to 99.99)
1308
3304
PV Dead Band
H'00000000 to H'0000270F (0 to 9999)
130A
3305
Cold Junction
Compensation Method
H'00000000 (0): OFF
H'00000001 (1): ON
1312
3309
Integral/Derivative Time
Unit
H'00000000 (0): 1 s
H'00000001 (1): 0.1 s
1314
330A
α
H'00000000 to H'00000064 (0.00 to 1.00)
1318
330C
Manual Output Method
H'00000000 (0): HOLD
H'00000001 (1): INIT
131A
330D
Manual MV Initial Value
Standard control or close position-proportional control:
H'FFFFFFCE to H'0000041A (
−
5.0 to 105.0)
Heating and cooling control:
H'FFFFFBE6 to H'0000041A (
−
105.0 to 105.0)
131E
330F
AT Calculated Gain
H'00000001 to H'00000064 (0.1 to 10.0)
1320
3310
AT Hysteresis
H'00000001 to H'0000270F (0.1 to 999.9 for temperature input)
H'00000001 to H'000003E7 (0.01 to 9.99 for analog input)
1322
3311
Limit Cycle MV Amplitude
H'00000032 to H'000001F4 (5.0 to 50.0)
1328
3314
Heater Burnout Latch
H'00000000 (0): OFF
H'00000001 (1): ON
132A
3315
Heater Burnout
Hysteresis
H'00000001 to H'000001F4 (0.1 to 50.0)
132C
3316
HS Alarm Latch
H'00000000 (0): OFF
H'00000001 (1): ON
132E
3317
HS Alarm Hysteresis
H'00000001 to H'000001F4 (0.1 to 50.0)
1334
331A
Operation End Operation
H'00000000 (0): RESET
H'00000001 (1): Continue control at final SP
H'00000002 (2): Fixed SP mode
*2
Initial setting
1338
331C
HB ON/OFF
H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
function
setting
133A
331D
Program End ON Time
H'00000000 to H'00000064 (0.0 to 10.0)
H'FFFFFFFF (
−
1): ON
133C
331E
Integrated Alarm
Assignment
H'00000000 to H'000000FF (0 to 255)
1344
3322
RT
H'00000000 (0): OFF
H'00000001 (1): ON
Note: Valid only with temperature input.
1346
3323
HS Alarm Use
H'00000000 (0): OFF
H'00000001 (1): ON
1348
3324
LBA Detection Time
H'00000000 to H'0000270F (0 to 9999)
134A
3325
LBA Level
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
134C
3326
LBA Band
H'00000000 to H'0000270F
(0.0 to 999.9 for temperature input)
(0.00 to 99.99 for analog input)
*1
Selection is not possible when ON/OFF control is set.
*2
Selection is not possible if the Reset Operation parameter is set to fixed SP operation.