6 Programless Communications
6 - 12
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
Example of Changing a Setting:
To set the Program 0 Alarm Value 3 parameter for Download Setting 11, you would change the set
value from 36 (Heater Burnout Detection 1) to 84 (Program 0 Alarm Value 3).
Data range and format of segment time
Data range and format of segment time set on the PLC side are as follows.
Installation values are set in BCD (Binary Code Decimal).
Hexadecimal A, B, C, D, E, and F cannot be used.
Parameter name
Displayed
characters
Setting
range
Default
Download Setting 16
dn16
30 to 179
101
Program 0 Segment 0 SP
Download Setting 17
dn17
103
Program 0 Segment 0 Time
Download Setting 18
dn18
106
Program 0 Segment 1 SP
Download Setting 19
dn19
108
Program 0 Segment 1 Time
Download Setting 20
dn20
111
Program 0 Segment 2 SP
Download Setting 21
dn21
113
Program 0 Segment 2 Time
Download Setting 22
dn22
116
Program 0 Segment 3 SP
Download Setting 23
dn23
118
Program 0 Segment 3 Time
Download Setting 24
dn24
121
Program 0 Segment 4 SP
Download Setting 25
dn25
123
Program 0 Segment 4 Time
Download Setting 26
dn26
126
Program 0 Segment 5 SP
Download Setting 27
dn27
128
Program 0 Segment 5 Time
Download Setting 28
dn28
131
Program 0 Segment 6 SP
Download Setting 29
dn29
133
Program 0 Segment 6 Time
Download Setting 30
dn30
136
Program 0 Segment 7 SP
Download Setting 31
dn31
138
Program 0 Segment 7 Time
Download Setting 32
dn32
141
Program 0 Segment 8 SP
Download Setting 33
dn33
143
Program 0 Segment 8 Time
Download Setting 34
dn34
146
Program 0 Segment 9 SP
Download Setting 35
dn35
148
Program 0 Segment 9 Time
Download Setting 36
dn36
30
Nothing assigned.
Download Setting 37
dn37
30
Nothing assigned.
Download Setting 38
dn38
30
Nothing assigned.
Download Setting 39
dn39
30
Nothing assigned.
Download Setting 40
dn40
30
Nothing assigned.
Download Setting 41
dn41
30
Nothing assigned.
Download Setting 42
dn42
30
Nothing assigned.
Download Setting 43
dn43
30
Nothing assigned.
Minim
u
m
4
b
its
16
b
its (2
b
ytes)
Setting range
Units are either on the left.
0
0
0
0
9
5
9
9
Maxim
u
m
Ho
u
rs
Min
u
tes
Min
u
tes
Seconds
Summary of Contents for E5CC-T
Page 2: ......
Page 184: ...Index 4 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Page 185: ......