A-9
Appendices
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-4
In
ver
ter P
arameter List
App
A-4
Inverter Parameter List
Inverter parameters are allocated to objects 3000 to 3102 hex and 4000 to 4102 hex.
3000 to 3102 hex are 16-bit parameters and 4000 to 4102 hex are 32-bit parameters.
Index and sub-index calculation method
Index: 3000 hex + (N/254), Sub-index: 1 + (N%254)
Index: 4000 hex + (N/254), Sub-index: 1 + (N%254)
N: Inverter register number
(N/254): Integer part after N is divided by 254
(N%254): Remainder after N is divided by 254
Holding register number list (frequency reference and fault monitor)
Index
Sub-
index
Register
No.
Function name
Parameter
No.
R/W
Monitor and setting items
Data
resolution
PDO
map
4000
hex
02
hex
0001 hex
Output Frequency
Setting
F001
RW
0 to maximum frequency (enabled
when A001 = 03)
0.01 [Hz]
Possible
(TxPDO)
3000
hex
05
hex
0004 hex
Inverter Status B
RO
0: Stopped
1: During operation
2: During trip
Possible
(TxPDO)
3000
hex
06
hex
0005 hex
Inverter Status C
RO
0:
1: Stop
2: Deceleration
3: Constant speed
4: Acceleration
5: Forward
6: Reverse
7: Forward to reverse
8: Reverse to forward
9: Forward run start
10: Reverse run start
Possible
(TxPDO)
3000
hex
07
hex
0006 hex
PID Feedback
RO
0 to 10000
0.01 [%]
Possible
(TxPDO)
3000
hex
12
hex
0011 hex
Fault Counter
d080
RO
0 to 65530
1 [time]
Possible
(TxPDO)
3000
hex
13
hex
0012 hex
Fault Monitor 1
Cause
d081
RO
Refer to
Inverter Fault Factor List
in
the operation manual for the MX2
inverter.
Possible
(TxPDO)
3000
hex
14
hex
0013 hex
Fault Monitor 1
Inverter Status
Refer to
Inverter Fault Factor List
in
the operation manual for the MX2
inverter.
Possible
(TxPDO)
4000
hex
15
hex
0014 hex
Fault Monitor 1
Frequency
0 to 100000
0.01 [Hz]
Possible
(TxPDO)
3000
hex
17
hex
0016 hex
Fault Monitor 1
Current
Output current value at the time of
tripping
0.01 [A]
Possible
(TxPDO)
3000
hex
18
hex
0017 hex
Fault Monitor 1 Voltage
DC input voltage at the time of
tripping
0.1 [V]
Possible
(TxPDO)
4000
hex
19
hex
0018 hex
Fault Monitor 1
RUN Time
Total RUN time at the time of
tripping
1 [h]
Possible
(TxPDO)
4000
hex
1B
hex
001A
hex
Fault Monitor 1
ON Time
Power ON time at the time of
tripping
1 [h]
Possible
(TxPDO)
Summary of Contents for 3G3AX-MX2-ECT
Page 23: ...20 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT CONTENTS ...
Page 31: ...1 EtherCAT Network 1 8 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 85: ...4 Inverter Control 4 18 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 111: ...5 CiA402 Drive Profile 5 26 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 162: ...Index 1 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT I Index ...
Page 164: ......