5 CiA402 Drive Profile
5 - 20
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
•
This object gives the present state of the unit.
•
Bit descriptions
•
This object gives the output frequency of the inverter.
•
The value in parenthesis indicates the unit when the inverter mode selection is High frequency mode.
•
Gives the cause of not being able to transit to Op when PDOs are freely mapped.
•
Gives up to 6 PDO mapping error messages.
•
Sub-index 1 (error cause) gives the latest cause code.
•
Sub-index 4 (number of error messages) gives the number of error messages that are registered.
•
Sub-indexes 5 to 10 (PDO mapping error message 1 to 6) give the cause codes when errors occur in
PDO mapping. Messages are saved in sequence from 1 to 6, and no more are saved. The history is
cleared when the power supply is turned OFF or the state transitions from initialization (Init) to
pre-operational (Pre-Op) is made.
5100 hex
Status
Setting range: 0000 to FFFF hex
Unit:
Default setting: 0000 hex
Size: 2 bytes (U16)
Access: RO
PDO map: Possible
Bit
Meaning
Details
0
During forward operation
0: Stop/reverse 1: During Forward operation
1
During reverse operation
0: Stop/forward 1: During Reverse operation
2
Reserved
Not used.
3
Fault
1: A fault (inverter trip) occurred.
4 to 6
Reserved
Not used.
7
Warning
1: A warning occurred.
9
Remote
0: Commands other than those from the EtherCAT Communication Unit are
enabled.
1: Commands from the EtherCAT Communication Unit are enabled.
10 to 11
Reserved
Not used.
12
Frequency matching
0: During Acceleration/deceleration or stopped 1: Frequency matching
13 to 14
Reserved
Not used.
15
Connection error between the
Optional Unit and inverter
1: Error (Cannot update data for the inverter. To reset the error, turn the
power supply OFF and then ON again.)
5110 hex
Output frequency monitor
Setting range: 0000 to FFFF hex
Unit: 0.01 Hz (0.1 Hz)
Default setting: 0000 hex
Size: 2 bytes (U16)
Access: RO
PDO map: Possible
5200 hex
PDO mapping error history
Sub-index 0: Number of entries
Setting range:
Unit:
Default setting: 0A hex
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Sub-index 1: Newest PDO mapping error cause
Setting range:
Unit:
Default setting: 0000 hex
Size: 2 bytes (U16)
Access: RO
PDO map: Not possible
Sub-index 4: Number of error message
Setting range:
Unit:
Default setting: 00 hex
Size: 2 bytes (U16)
Access: RO
PDO map: Not possible
Sub-indexes 5 to A: PDO mapping error message 1 to 6
Unit:
Unit:
Default setting: 0000 hex
Size: 2 bytes (U16)
Access: RO
PDO map: Not possible
All
All
All
Summary of Contents for 3G3AX-MX2-ECT
Page 23: ...20 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT CONTENTS ...
Page 31: ...1 EtherCAT Network 1 8 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 85: ...4 Inverter Control 4 18 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 111: ...5 CiA402 Drive Profile 5 26 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 162: ...Index 1 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT I Index ...
Page 164: ......