Appendices
A-12
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Inverter fault factor list
Trip factor high-order (factor)
Trip factor low-order (Inverter status)
Name
Code
Name
Code
No trip factor
0
During reset
0
Overcurrent protection during constant
speed
1
During stop
1
Overcurrent protection during decelera-
tion
2
During deceleration
2
Overcurrent protection during accelera-
tion
3
At a constant speed
3
Overcurrent protection during stop
4
During acceleration
4
Overload protection
5
Operates at frequency = 0
5
Braking resistor overload protection
6
During startup
6
Overvoltage protection
7
DB active (DC injection braking active)
7
EEPROM error
8
During overload limit
8
Undervoltage protection
9
Current detector error
10
CPU error
11
External trip
12
USP error
13
Grounding protection
14
Incoming overvoltage protection
15
Abnormal temperature
21
Main circuit error
25
Driver error
30
Thermistor error
35
Brake error
36
Emergency shutoff
37
Overload protection in a low speed
range
38
Digital operator connection error
40
Modbus communication (Modbus-RTU)
error
41
Internal data error
43 to 45
50 to 69
Encoder disconnection
80
Overspeed
81
Position control range trip
83
Summary of Contents for 3G3AX-MX2-ECT
Page 23: ...20 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT CONTENTS ...
Page 31: ...1 EtherCAT Network 1 8 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 85: ...4 Inverter Control 4 18 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 111: ...5 CiA402 Drive Profile 5 26 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 162: ...Index 1 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT I Index ...
Page 164: ......