2 - 19
2 Starting a Sample System
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2-6 SYSDRIVE MX2 Series Settings
2
2-6-1 R
U
N Command Set
ting
2-6
SYSDRIVE MX2 Series Settings
To perform control from the Communication Unit, the parameter settings must be changed from the
front panel digital operator of the inverter.
In this procedure, the inverter power supply must be turned ON. When the power supply is turned ON,
the inverter may operate in unintended way. Check the condition of the wiring and system carefully
before starting the procedure.
Refer to the User Manual (Cat No.I570) for the SYSDRIVE MX2-series inverter for details on operating
the inverter parameter settings and for the meaning of the parameter values.
Change the control method for the RUN command.
Change the control method for the frequency reference.
Set the operation of the reset signal.
*
If parameter C102 is not displayed, first set parameter b037 to 01.
2-6-1
RUN Command Setting
Parameter No.
Function name
Data
Default value
A002
RUN Command Selection 1
04 (Optional boad)
02 (Digital Operator)
2-6-2
Frequency Reference Setting
Parameter No.
Function name
Data
Default value
A001
Frequency Reference Selection 1
04 (Optional boad)
02 (Digital Operator)
2-6-3
Reset Selection Setting
Parameter No.
Function name
Data
Default value
C102
Reset Selection
03 (Trip reset only)
00 (Trip reset at power-ON)
Summary of Contents for 3G3AX-MX2-ECT
Page 23: ...20 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT CONTENTS ...
Page 31: ...1 EtherCAT Network 1 8 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 85: ...4 Inverter Control 4 18 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 111: ...5 CiA402 Drive Profile 5 26 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 162: ...Index 1 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT I Index ...
Page 164: ......