A-21
Appendices
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-4
In
ver
ter P
arameter List
App
3013
hex
6B
hex
1344 hex
Window Comparator
FI Hysteresis Width
b065
RW
0. to 10.
(Upper limit: (b063
b064) / 2)
1 [%]
Possible
3013
hex
70
hex
1349 hex
Analog Operation Level
at FV Disconnection
b070
RW
0 to 100/255 (no)
1 [%]
Possible
(TxPDO)
3013
hex
71
hex
134A
hex
Analog Operation
Level at FI
Disconnection
b071
RW
0 to 100/255 (no)
1 [%]
Possible
(TxPDO)
3013
hex
75
hex
134E
hex
Ambient Temperature
b075
RW
10 to 50
1 [
C]
Possible
3013
hex
78
hex
1351 hex
Integrated Power Clear
b078
RW
00: Disabled
01: Clear (Return to 00 after clear)
Possible
3013
hex
79
hex
1352 hex
Integrated Power
Display Scale
b079
RW
1 to 1000
1
Possible
3013
hex
7C
hex
1355 hex
Starting Frequency
b082
RW
10 to 999 (10000)
0.01 [Hz]
Possible
(TxPDO)
3013
hex
7D
hex
1356 hex
Carrier Frequency
b083
RW
20 to 150
0.1 [kHz]
Possible
(TxPDO)
3013
hex
7E
hex
1357 hex
Initialization Selection
b084
RW
00: Initialization disabled
01: Clear fault monitor
02: Initialize data
03: Clear fault m initialize
data
04: Do not set.
Possible
(TxPDO)
3013
hex
7F
hex
1358 hex
Initialization Data
Selection
b085
RW
00: Do not change.
Possible
(TxPDO)
3013
hex
80
hex
1359 hex
Frequency Conversion
Coefficient
b086
RW
1 to 9999
0.01
Possible
3013
hex
81
hex
135A
hex
STOP Key Selection
b087
RW
00: Enabled
01: Disabled
02: Only reset is enabled
Possible
(TxPDO)
3013
hex
82
hex
135B
hex
Free-run Stop
Selection
b088
RW
00: 0 Hz restart
01: Frequency matching restart
02: Frequency pull-in restart
Possible
(TxPDO)
3013
hex
83
hex
135C
hex
Automatic Carrier
Reduction
b089
RW
00: Disabled
01: Enabled, depends on the
current
02: Enabled, depends on the fin
temperature
Possible
(TxPDO)
3013
hex
84
hex
135D
hex
Usage Rate of
Regenerative Braking
b090
RW
0 to 1000
0.1 [%]
Possible
(TxPDO)
3013
hex
85
hex
135E
hex
Stop Selection
b091
RW
00: Deceleration stop
01: Free-run stop
Possible
(TxPDO)
3013
hex
86
hex
135F hex
Cooling Fan Operation
b092
RW
00: Always
01: Only during operation
(Including 5 minutes after the
power is turned on and also
after the inverter stops)
02: Depends on the fin temperature
Possible
(TxPDO)
3013
hex
87
hex
1360 hex
Cooling Fan Total
Operating Time Clear
b093
RW
00: Operating time count
01: Clear (Return to 00 after clear)
Possible
(TxPDO)
3013
hex
88
hex
1361 hex
Initialization Target
Selection
b094
RW
00: All data
01: Data other than
terminal/communications
02: U
***
registration function only
03: Other than U
***
registration
function
Possible
(TxPDO)
3013
hex
89
hex
1362 hex
Regenerative Braking
Selection
b095
RW
00: Disabled
01: Enabled (Disabled during stop)
02: Enabled (Enabled during stop)
Possible
(TxPDO)
3013
hex
8A
hex
1363 hex
Regenerative Braking
ON Level
b096
RW
330 to 380/660 to 760
1 [V]
Possible
(TxPDO)
3013
hex
8E
hex
1367 hex
Free V/f Frequency 1
b100
RW
0 to Free V/f Frequency 2
1 [Hz]
Possible
(TxPDO)
3013
hex
8F
hex
1368 hex
Free V/f Voltage 1
b101
RW
0 to 8000
0.1 [V]
Possible
(TxPDO)
3013
hex
90
hex
1369 hex
Free V/f Frequency 2
b102
RW
0 to Free V/f Frequency 3
1 [Hz]
Possible
(TxPDO)
3013
hex
91
hex
136A
hex
Free V/f Voltage 2
b103
RW
0 to 8000
0.1 [V]
Possible
(TxPDO)
Index
Sub-
index
Register
No.
Function name
Parameter
No.
R/W
Monitor and setting items
Data
resolution
PDO
map
Summary of Contents for 3G3AX-MX2-ECT
Page 23: ...20 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT CONTENTS ...
Page 31: ...1 EtherCAT Network 1 8 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 85: ...4 Inverter Control 4 18 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 111: ...5 CiA402 Drive Profile 5 26 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 162: ...Index 1 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT I Index ...
Page 164: ......