2 Starting a Sample System
2 - 4
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
These switches are used to set the node addresses of slaves in the EtherCAT network (decimal).
The 10s digit is set on the left rotary switch and the 1s digit is set on the right rotary switch.
The setting range is 00 to 99.
Note that the node address settings vary as shown below when the Host Controller is made by OMRON
and when it is made by other manufacturers.
Precautions for Correct Use
•
The set node address is read only once when the inverter power supply is turned ON.
If the setting is changed after the power supply is turned ON, the new setting will not be used
until the next time that the power is turned ON.
•
Do not change the setting on the rotary switches after the power supply has been turned ON.
•
If node addresses overlap, an error occurs and the operation stops.
2-1-3
Rotary Switches for Node Address Setting
Set value for rotary switch
Set value for node address
OMRON Host Controller
Host Controller from another
manufacturer
00
The Host Controller set value is used as the
node address.
The Host Controller set value is used
regardless of the rotary switch set value.
01 to 99
The rotary switch set value is used as the
node address.
Node
a
ddre
ss
s
etting
(× 1)
Node
a
ddre
ss
s
etting
(× 10)
Summary of Contents for 3G3AX-MX2-ECT
Page 23: ...20 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT CONTENTS ...
Page 31: ...1 EtherCAT Network 1 8 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 85: ...4 Inverter Control 4 18 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 111: ...5 CiA402 Drive Profile 5 26 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 162: ...Index 1 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT I Index ...
Page 164: ......