A-19
Appendices
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-4
In
ver
ter P
arameter List
App
3013
hex
32
hex
130B
hex
Overvoltage/Overcurrent
Restart Count Selection
b010
RW
1 to 3
1 [time]
Possible
(TxPDO)
3013
hex
33
hex
130C
hex
Overvoltage/Overcurrent
Restart Standby Time
b011
RW
3 to 1000
0.1 [s]
Possible
(TxPDO)
3013
hex
34
hex
130D
hex
Electronic Thermal
Level 1
b012
RW
200 to 1000
0.1 [%]
Possible
(TxPDO)
3013
hex
35
hex
130E
hex
Electronic Thermal
Characteristics
Selection 1
b013
RW
00: Reduced torque characteristics
01: Constant torque characteristics
02: Free setting
Possible
(TxPDO)
3013
hex
37
hex
1310 hex
Free-electronic
Thermal Frequency 1
b015
RW
0 to Free-electronic Thermal
Frequency 2
1 [Hz]
Possible
(TxPDO)
3013
hex
38
hex
1311 hex
Free-electronic
Thermal Current 1
b016
RW
0.00 to rated current
0.01 [%]
Possible
(TxPDO)
3013
hex
39
hex
1312 hex
Free-electronic
Thermal Frequency 2
b017
RW
Free-electronic Thermal Frequency
1 to Free Setting, Electric Thermal
Frequency 3
1 [Hz]
Possible
(TxPDO)
3013
hex
3A
hex
1313 hex
Free-electronic
Thermal Current 2
b018
RW
0.00 to rated current
0.01 [%]
Possible
(TxPDO)
3013
hex
3B
hex
1314 hex
Free-electronic
Thermal Frequency 3
b019
RW
Free-electronic Thermal Frequency
2 to 400 (1000)
1 [Hz]
Possible
(TxPDO)
3013
hex
3C
hex
1315 hex
Free-electronic
Thermal Current 3
b020
RW
0.00 to rated current
0.01 [%]
Possible
(TxPDO)
3013
hex
3D
hex
1316 hex
Overload Limit 1
Selection
b021
RW
00: Disabled
01: Enabled during
acceleration/constant speed
02: Enabled during constant speed
03: Enabled during
acceleration/constant speed
(accelerated during
regeneration)
Possible
(TxPDO)
3013
hex
3E
hex
1317 hex
Overload Limit 1 Level
b022
RW
200 to 2000
0.01 [%]
Possible
(TxPDO)
3013
hex
3F
hex
1318 hex
Overload Limit 1
Parameter
b023
RW
1 to 30000
0.1 [s]
Possible
(TxPDO)
3013
hex
40
hex
1319 hex
Overload Limit 1
Selection 2
b024
RW
00: Disabled
01: Enabled during
acceleration/constant speed
02: Enabled during constant speed
03: Enabled during
acceleration/constant speed
(accelerated during
regeneration)
Possible
(TxPDO)
3013
hex
41
hex
131A
hex
Overload Limit 1
Level 2
b025
RW
200 to 2000
0.01 [%]
Possible
(TxPDO)
3013
hex
42
hex
131B
hex
Overload Limit 1
Parameter 2
b026
RW
1 to 30000
0.1 [s]
Possible
(TxPDO)
3013
hex
43
hex
131C
hex
Overcurrent
Suppression Selection
b027
RW
00: Disabled
01: Enabled
Possible
(TxPDO)
3013
hex
44
hex
131D
hex
Frequency Pull-in
Restart Level
b028
RW
200 to 2000
0.01 [%]
Possible
(TxPDO)
3013
hex
45
hex
131E
hex
Frequency Pull-in
Restart Parameter
b029
RW
1 to 30000
0.1 [s]
Possible
(TxPDO)
3013
hex
46
hex
131F hex
Starting Frequency at
Frequency Pull-in
Restart Selection
b030
RW
00: Frequency at interruption
01: Max. frequency
02: Set frequency
Possible
(TxPDO)
3013
hex
47
hex
1320 hex
Soft Lock Selection
b031
RW
00: Data other than b031 cannot be
changed when terminal SFT is
ON.
01: Data other than b031 and the
set frequency cannot be
changed when terminal SFT is
ON.
02: Data other than b031 cannot be
changed.
03: Data other than b031 and the
set frequency cannot be
changed.
10: Data can be changed during
RUN.
Possible
(TxPDO)
3013
hex
49
hex
1322 hex
Motor Cable Length
Code Selection
b033
RW
5 to 20
Possible
(TxPDO)
Index
Sub-
index
Register
No.
Function name
Parameter
No.
R/W
Monitor and setting items
Data
resolution
PDO
map
Summary of Contents for 3G3AX-MX2-ECT
Page 23: ...20 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT CONTENTS ...
Page 31: ...1 EtherCAT Network 1 8 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 85: ...4 Inverter Control 4 18 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 111: ...5 CiA402 Drive Profile 5 26 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 162: ...Index 1 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT I Index ...
Page 164: ......