6 - 5
6 Handling of Errors and Maintenance
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
6-2 Me
ssa
g
e Err
o
rs
6
6-2
Message Errors
The abort codes for when an SDO communications error occurs are shown below.
Value
Meaning
05030000 hex
Toggle bit not changed
05040000 hex
SDO protocol timeout
05040001 hex
Client/Server command specifier not valid or unknown
05040005 hex
Out of memory
06010000 hex
Unsupported access to an object
06010001 hex
Attempt to read a write only object
06010002 hex
Attempt to write to a read only object
06020000 hex
The object does not exist in the object directory
06040041 hex
The object can not be mapped into the PDO.
06040042 hex
The number and length of the objects to be mapped would exceed the PDO length.
06040043 hex
General parameter incompatibility reason
06040047 hex
General internal incompatibility in the device
06060000 hex
Access failed due to a hardware error
06070010 hex
Data type does not match, length of service parameter does not match
06070012 hex
Data type does not match, length of service parameter too high
06070013 hex
Data type does not match, length of service parameter too low
06090011 hex
Subindex does not exist
06090030 hex
Value range of parameter exceeded (only for write access)
06090031 hex
Value of parameter written too high
06090032 hex
Value of parameter written too low
06090036 hex
Maximum value is less than minimum value
08000000 hex
General error
08000020
hex
Data cannot be transferred or stored to the application
08000021
hex
Data cannot be transferred or stored to the application because of local control
08000022
hex
Data cannot be transferred or stored to the application because of the present device state
08000023
hex
Object dictionary dynamic generation fails or no object dictionary is present
Summary of Contents for 3G3AX-MX2-ECT
Page 23: ...20 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT CONTENTS ...
Page 31: ...1 EtherCAT Network 1 8 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 85: ...4 Inverter Control 4 18 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 111: ...5 CiA402 Drive Profile 5 26 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 162: ...Index 1 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT I Index ...