4 Inverter Control
4 - 10
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
4-3
Control with the Independent Profile
This section describes how to use the OMRON profile to control the inverter.
The inverter parameters must be set to match the profile.
With the independent profile, set as follows.
*
If parameter C102 is not displayed, set b037 to 01.
Assign the PDOs of the independent profile to Sync Manager.
The values below are the fixed mapping for the PDOs.
Control the inverter by operating the PDOs that allocate the profile.
Control information (master to slave)
Status information (slave to master)
4-3-1
Inverter Setting
Parameter
Description
A001 Frequency Reference Selection 1
04: Optional boad
A002 RUN Command Selection 1
04: Optional boad
C102 Reset Selection
03: Trip reset only
4-3-2
Profile Allocation
Sync Manager PDO assignment
Description
1C12 hex
1701 hex (Fixed allocation of the independent profile)
1C13 hex
1B01 hex (Fixed allocation of the independent profile)
PDO
Description
1701 hex
5000 hex (Command)
5010 hex (Frequency reference)
1B01 hex
5100 hex (Status)
5110 hex (Output frequency monitor)
4-3-3
Control Method
IO format
Word
Meaning
n
Command
n + 1
Frequency reference
Word
Meaning
m
Status
m + 1
Output frequency monitor
Summary of Contents for 3G3AX-MX2-ECT
Page 23: ...20 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT CONTENTS ...
Page 31: ...1 EtherCAT Network 1 8 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 85: ...4 Inverter Control 4 18 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 111: ...5 CiA402 Drive Profile 5 26 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Page 162: ...Index 1 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT I Index ...
Page 164: ......