5 Parameter
BU 0200 en-US-4920
165
Pos : 418 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P300- P399/Param et er P353 – Busz ust and über PLC @ 9\mod_1448363834229_14638. doc x @ 266483 @ @ 1
P353
Bus status via PLC
(Bus status via PLC)
S
0 ... 3
{ 0 }
This parameter can be used to determine how the control word (CTW) for the master function and
the status word (STW) of the variable frequency drive undergo further processing by the PLC.
0 = Off:
The control word (CTW) of the master function (P503≠0) and the status word (STW)
undergo further processing by the PLC without change.
1 = CTW for broadcast:
The control word (CTW) for the master value function (P503≠ 0) is set
by the PLC. In order to do this, the control word must be redefined accordingly in the PLC
using process value "34_PLC_Busmaster_Control_word".
2 = STW for bus:
The status word (STW) of the variable frequency drive is set by the PLC. In
order to do this, the status word must be redefined accordingly in the PLC using process
value "28_PLC_status_word".
3 = CTW Broadcast&STWBus:
See setting 1 and 2
Pos : 419 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P300- P399/Param et er P355 – PLC Int eger Sollwert @ 9\m od_1448364290270_14638. docx @ 266516 @ @ 1
P355
[-01]
...
[-10]
PLC integer setvalue
(PLC integer setpoint)
S
0x0000 … 0xFFFF
all = { 0 }
Data can be exchanged with the PLC via this INT array. This data can be used by the appropriate
process variables in the PLC.
Pos : 420 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P300- P399/Param et er P356 – PLC Long Sollw ert @ 9\mod_1448376305117_14638. doc x @ 266622 @ @ 1
P356
[-01]
...
[-05]
PLC long setvalue
(PLC long setpoint)
S
0x0000 0000 …
0xFFFF FFFF
all = { 0 }
Data can be exchanged with the PLC via this DINT array. This data can be used by the
appropriate process variables in the PLC.
Pos : 421 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P300- P399/Param et er P360 – PLC Anzeigew ert @ 9\m od_1448376691352_14638. docx @ 266655 @ @ 1
P360
[-01]
...
[-05]
PLC display value
(PLC display value)
S
-2 000 000,000 …
2 000 000.000
all = { 0.000 }
The parameter is only used to display the PLC date. This parameter can be written by the PLC
via the corresponding process variables. The values are not saved!
Pos : 422 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P300- P399/Param et er P370 – PLC St at us @ 9\mod_1448364654868_14638. docx @ 266549 @ @ 1
P370
PLC status
(PLC status)
S
0 … 63
dec
Parameter Box:
0x00 … 0x3F
Simple Box/Control Box:
0x00 … 0x3F
all = { 0 }
Displays the actual status of the PLC.
Bit 0 = P350=1:
Parameter P350 was set in the "Activate internal PLC" function
Bit 1 = PLC active:
The internal PLC is active.
Bit 2 = Stop active:
The PLC program is in "Stop" status.
Bit 3 = Debug active:
Error checking of the PLC program is running.
Bit 4 = PLC fault:
The PLC has an error but PLC user errors 23.xx are not displayed here.
Bit 5 = PLC stopped:
The PLC program was stopped (
single step
or
breakpoint
).