Information
V/f characteristic curve
With certain applications, particularly those with high centrifugal mass (e.g. fan drives), it may be
necessary to control the motor with the aid of a U/f characteristic curve. In order to do this, set
parameters
P211
and
P212
each to 0%.
Pos : 356 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P200- P299/Param et er P212 – Sc hl upf kom pens ati on - I nf ormati on PM SM @ 58\m od_1606204181342_14638.docx @ 2695397 @ @ 1
Information
PMSM
When controlling a PMSM, this parameter determines the voltage of the test signal method
(
P330
). The required voltage depends on various factors (ambient and motor temperature, motor
size, motor cable length, size of variable frequency drive). If the rotor position identification is not
successful, this parameter can be used to adjust the voltage.
Pos : 357 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P200- P299/Param et er P213 – Verst. I SD-Regel ung @ 0\m od_1327590323026_14638. docx @ 14925 @ @ 1
P213
ISD ctrl. loop gain
(amplification ISD control)
S
P
25 ... 400 %
{ 100 }
This parameter affects the control dynamics of the VFD current vector control (ISD control). Higher
settings make the controller faster, lower settings slower.
Depending on the type of application, this parameter can be adjusted to avoid unstable operation
for example.
Pos : 358 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P200- P299/Param et er P214 – Vorhalt Dr ehm om ent @ 0\mod_1327590368794_14638.docx @ 14926 @ @ 1
P214
Torque precontrol
(torque derivative action)
S
P
-200 ... 200 %
{ 0 }
This function allows a value for the expected torque requirement to be set in the current controller.
This function can be used in lifting gears for better load transfer during startup.
NOTE:
In clockwise rotary field direction, motor torques are entered with a positive sign, while
regenerative torques are entered with a negative sign. The reverse applies to
counterclockwise rotation.
Pos : 359 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P200- P299/Param et er P215 – Boost Vorhalt @ 0\mod_1327590415702_14638. doc x @ 14927 @ @ 1
P215
Boost precontrol
(boost derivative action)
S
P
0 ... 200 %
{ 0 }
Only advisable in linear characteristic curves (P211 = 0% and P212 = 0%).
For drives that require a high starting torque, this parameter provides an option for adding an
additional current during the start phase. The operative time is limited and can be selected in
parameter P216 >Boost derivative action time<.
All current and torque current limits that may have been set (P112, P536, P537) are deactivated
during the boost derivative action time.
NOTE:
With active ISD c
ontrol (P211 and/or P212 ≠ 0%), parameterization of P215 ≠ 0 results in incorrect
control.
Pos : 360 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1
Pos : 361 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P200- P299/Param et er P216 – Zei t Boost Vorhalt @ 2\m od_1346931673560_14638. docx @ 42281 @ @ 1
P216
Time boost prectrl.
(boost derivative action time)
S
P
0.0 ... 10.0 s
{ 0.0 }
This parameter is used for 3 functions:
Time limit
for
boost derivative action
:
Operative time for increased starting current.
Only in linear characteristic curves (P211 = 0% and P212 = 0%).
Time limit
for
suppression
of
pulse switch-off
(P537): enables heavy starting.
Time limit
for
suppression
of
switch-off on error
in parameter (P401), setting { 05 } "0 - 10 V
with switch-off on error 2"
Pos : 362 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P200- P299/Param et er P217 – Sc hwi ngungs dämpf ung @ 0\m od_1327590520707_14638.docx @ 14929 @ @ 1