Pos : 151 /Anleit ungen/El ektr onik /FU und St art er/2. M ontage und I nst allation/ Elek trischer Ans chl uss/ SK 1xxE, SK 2xx E, SK 5xxP, SK xxx E-FDS/ Leist ungst eil/ Elektrisc her Ansc hluss Leis tungst eil_T eil3 - Mot ork abel_01 [ SK 1x0E, SK 2xxE, SK 2xx E-FDS, SK 5xx P] @ 48\m od_1596699827741_14638. docx @ 2658078 @ 4 @ 1
2.4.2.2
Motor cable
The motor cable may have a total
length of
25 m
if it is a standard cable type (take EMC into
consideration). If a shielded motor cable is used or if the cable is laid in a well-grounded metal duct,
the total length should not exceed
5 m
(cable shield connected to PE bilaterally).
Pos : 152 /Anleit ungen/El ektr onik /FU und St art er/1. Allgemei nes /Sic herheits- und Ins tall ations hinw eis e und W arn- Gefahrenhinw eise/neu/War n- und Gefahrenhinw eise/ACHTUN G - Sc halt en am Ausg ang [ FU] @ 33\mod_1557398548279_14638.docx @ 2534609 @ @ 1
NOTICE
Output switching
Switching a motor cable under load causes an impermissibly high load on the device. Components in
the power section may be damaged and destroyed either immediately or in the long term.
• Only switch the motor cable when the variable frequency drive no longer outputs power. I.e. the
device must be in the "ready to switch on" or "switch-on block" state.
Pos : 153 /Anleit ungen/El ektr onik /FU und St art er/2. M ontage und I nst allation/ Elek trischer Ans chl uss/ SK 1xxE, SK 2xx E, SK 5xxP, SK xxx E-FDS/ Leist ungst eil/ Elektrisc her Ansc hluss Leis tungst eil_T eil3 - Mot ork abel_03 [ SK 1x0E, SK 2xxE, SK 2xx E-FDS] @ 33\m od_1557404347303_14638. doc x @ 2534719 @ @ 1
Information
Synchronous motors or multiple-motor operation
If synchronous machines or several motors are connected in parallel to a device, the variable
frequency drive must be switched over to linear voltage/frequency characteristic curves,
(
P211 = 0 and P212 = 0).
For multiple-motor operation the total motor cable length is the sum of the individual motor cable
lengths.
Pos : 154 /Anleit ungen/El ektr onik /FU und St art er/2. M ontage und I nst allation/ Elek trischer Ans chl uss/ SK 1xxE, SK 2xx E, SK 5xxP, SK xxx E-FDS/ Leist ungst eil/ Elektrisc her Ansc hluss Leis tungst eil_T eil3 - Br emswiderst and_01 [ SK 1x0E, SK 2xxE] @ 7\mod_1434537485678_14638. doc x @ 226615 @ 4 @ 1
2.4.2.3
Braking resistor (+B, -B)
– (from size
1
)
The +B/-B terminals are used to connect a suitable braking resistor. Select the shortest possible,
shielded link for the connection.
Pos : 155 /Anleit ungen/El ektr onik /FU und St art er/1. Allgemei nes /Sic herheits- und Ins tall ations hinw eis e und W arn- Gefahrenhinw eise/neu/War n- und Gefahrenhinw eise/VORSICHT - H eiße O ber fläc hen ( Bremswi ders tand) @ 28\m od_1551424569795_14638. docx @ 2493080 @ @ 1
CAUTION
Hot surfaces
The braking resistor and all other metal components can heat up to temperatures above 70°C.
• Risk of injury due to local burns on contact.
• Heat damage to adjacent objects
Allow sufficient cooling time before starting work on the product. Check the surface temperatures with
suitable measuring equipment. Maintain an adequate distance to adjacent components.