NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
150
BU 0200 en-US-4920
Pos : 341 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P200- P299/Param et er P203 – Motor N enns trom @ 41\mod_1586433053290_14638. doc x @ 2601030 @ @ 1
P203
Nominal current
(rated motor current)
S
P
0.1 ... 1000.0 A
{ see information }
The rated motor current is a decisive parameter for current vector control.
Information
Default setting
The default setting depends on the rated VFD output or the setting in
P200
.
Pos : 342 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P200- P299/Param et er P204 – Motor N enns pannung @ 41\mod_1586433246488_14638.docx @ 2601066 @ @ 1
P204
Nominal voltage
(rated motor voltage)
S
P
100 ... 800 V
{ see information }
The rated motor voltage adjusts the line voltage to the motor voltage. In combination with the rated
frequency, the voltage/frequency characteristic curve is produced.
Information
Default setting
The default setting depends on the rated VFD output or the setting in
P200
.
Pos : 343 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P200- P299/Param et er P205 – Motor N ennl eist ung @ 41\mod_1586433362067_14638.docx @ 2601102 @ @ 1
P205
Nominal power
(Rated motor output)
P
0.00 ... 250.00 kW
{ see information }
The rated motor output controls the motor set via
P200
.
Information
Default setting
The default setting depends on the rated VFD output or the setting in
P200
.
Pos : 344 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P200- P299/Param et er P206 – Motor c os phi @ 41\m od_1586434114694_14638.docx @ 2601138 @ @ 1
P206
Cos phi
(motor cos
ϕ
)
S
P
0.50 ... 0.95
{ see information }
The motor cos
ϕ
is a decisive parameter for current vector control.
Information
Default setting
The default setting depends on the rated VFD output or the setting in
P200
.
Pos : 345 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P200- P299/Param et er P206 – Motor c os phi_Info_PM SM @ 19\mod_1505894620817_14638.docx @ 2365515 @ @ 1
Information
PMSM
This parameter is not relevant if a PMSM is used.
Pos : 346 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P200- P299/Param et er P207 – Motorsc haltung @ 41\m od_1586434261620_14638.docx @ 2601174 @ @ 1
P207
Star Delta con.
(motor circuit )
S
P
0 ... 1
{ see information }
0 = star
1 = delta
The motor circuit is crucial for stator resistance measurement (
P220
) and therefore critical for
current vector control.
Information
Default setting
The default setting depends on the rated VFD output or the setting in
P200
.