4 Commissioning
BU 0200 en-US-4920
103
Pos : 228. 7 / Anleit ungen/El ektr onik /FU und St art er/4. I nbetri ebnahm e/ Inbetriebnahme Betriebs arten M ot orregler ( P300) [SK 1x 0E, SK 2xx E, SK 5xxE]/ Par ameter übersic ht R eglerei nst ellung [ SK 2x xE, SK 5xx E, SK 2xxE-FD S] @ 6\m od_1421067020960_14638. docx @ 198342 @ 3 @ 1
4.2.2 Overview of control parameter settings
The following provides an overview of all parameters which are of importance, depending on the
selected operating mode. Among other things, a distinction is made between "relevant" and
"important", which provides an indication of the required precision of the particular parameter setting.
However, in principle, the more precisely the setting is made, the more exact the control, and the
higher the values for dynamics and precision possible for the operation of the drive unit. A detailed
description of these parameters can be found in Section 5 "Parameter".
"Ø" =
Parameter has no significance
"-” =
Leave the parameter in the factory setting
"√" =
Setting of the parameter is relevant
"!" =
Setting of the parameter is important
Group
Parameter
Operating mode
VFC open-loop
CFC open-loop
CFC closed-loop
ASM
PMSM
ASM
PMSM
ASM
PMSM
M
o
to
r d
a
ta
P201 … P209
√
√
√
√
√
√
P208
!
!
!
!
!
!
P210
√
1)
√
√
√
Ø
Ø
P211, P212
-
2)
-
-
-
-
-
P215, P216
-
1)
-
-
-
-
-
P217
√
√
√
√
Ø
Ø
P220
√
√
√
√
√
√
P240
-
√
-
√
-
√
P241
-
√
-
√
-
√
P243
-
√
-
√
-
√
P244
-
√
-
√
-
√
P246
-
√
-
√
-
√
P245, 247
-
√
Ø
Ø
Ø
Ø
C
o
n
tr
o
ll
e
r d
a
ta
P300
√
√
√
√
√
√
P301
Ø
Ø
Ø
Ø
!
!
P310 … P320
Ø
Ø
√
√
√
√
P312, P313, P315, P316
Ø
Ø
-
√
-
√
P330 … P333
-
√
-
√
-
√
P334
Ø
Ø
Ø
Ø
-
√
1)
=
in V/f characteristic curve: precise setting of the parameter is important
2)
=
in V/f characteristic curve: typical setting 0
Pos : 228. 8 / Allgem ein/ Allgemei ngültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1