![nord NORDAC FLEX SK 2 E-111-123-A Series User Manual Download Page 211](http://html1.mh-extra.com/html/nord/nordac-flex-sk-2-e-111-123-a-series/nordac-flex-sk-2-e-111-123-a-series_user-manual_1701208211.webp)
5 Parameter
BU 0200 en-US-4920
211
Pos : 577 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P708 – Zust and Digital eing äng e [ SK 2x xE] @ 2\mod_1346932204549_14638.docx @ 43484 @ @ 1
P708
State of digital input
(digital input status)
00000 ... 11111
(bin)
or
0000 ... FFFF
(hex)
Displays the status of the digital inputs in binary/hexadecimal code. This display can be used to
check the input signals.
Bit 0 =
Digital input 1
Bit 1 =
Digital input 2
Bit 2 =
Digital input 3
Bit 3 =
Digital input 4
Bit 4 =
PTC resistor input
Bits 5 - 7
reserved
Pos : 578 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P708 – Zust and Digital eing äng e_T eil 2/ 2 [ SK 1x 0E, SK 2x xE, SK 2xx E-FDS] @ 9\mod_1448441143299_14638.docx @ 266699 @ @ 1
First SK xU4-IOE (optional)
Bit 8 =
1st IO extension: Digital input 1
Bit 9 =
1st IO extension: Digital input 2
Bit 10 =
1st IO extension: Digital input 3
Bit 11 =
1st IO extension: Digital input 4
Second SK xU4-IOE (optional)
Bit 12 =
2nd IO extension: Digital input 1
Bit 13 =
2nd IO extension: Digital input 2
Bit 14 =
2nd IO extension: Digital input 3
Bit 15 =
2nd IO extension: Digital input 4
Bits 15-12
Bits 11-8
Bits 7-4
Bits 3-0
Minimum value
0000
0
0000
0
0000
0
0000
0
Binary
hex
Maximum value
1111
F
1111
F
1111
F
1111
F
Binary
hex
Simple Box:
The binary bits are converted to a hexadecimal value and displayed.
Parameter Box:
The bits are displayed increasing from right to left (binary).
Pos : 579 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1
Pos : 580 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P709 – Spannung Analog eingang [ SK 2x xE] @ 2\mod_1346932205173_14638.docx @ 43508 @ @ 1
P709
[-01]
...
[-09]
Analog input voltage
(analog input voltage)
-100 ... 100 %
Displays the measured analog input value.
SK 2x0E
SK 2x5E
[-01] =
Analog input 1
, value of analog input
1 integrated in the VFD.
[-01] =
Potentiometer 1
, internal
potentiometer P1 in the VFD (chapter
4.3.2), for setting the maximum
frequency, minimum frequency and
ramp time
[-02] =
Analog input 2
, value of analog input
2 integrated in the VFD.
[-02] =
Potentiometer 2
, same as
potentiometer 1
SK 2xxE
[-03] =
Ext. Analog in 1,
AIN 1 of the first SK xU4-IOE I/O extension
[-04] =
Ext. Analog in 2,
AIN2 of the first SK xU4-IOE I/O extension
[-05] =
Setpoint module
SK 2xxE, size 1 – 3
SK 2x0E, size 4
[-06] =
Analog function dig.
.
2
, analog
function of VFD digital input 2
[-06] =
Potentiometer 1
, internal
potentiometer P1 in the VFD (chapter
4.3.2), for setting the maximum
frequency, minimum frequency and
ramp time
[-07] =
Analog function dig.
.
3
, analog
function of VFD digital input 3
[-07] =
Potentiometer 2
, same as
potentiometer 1