NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
106
BU 0200 en-US-4920
Pos : 236 /Anleit ungen/El ektr onik /FU und St art er/4. I nbetriebnahm e/ SK 1x xE, SK 2xx E, -FD S/I nbetriebnahme G erät /Konfiguration_01 [ SK 2x xE] @ 1\mod_1343218853713_14638.docx @ 37329 @ 3 @ 1
4.3.2 Configuration
Changes to individual parameters are usually necessary for operation.
However, configuration can be carried out to a limited extent by means of the integrated 8-pole DIP
switch (S1).
Information
Configuration via DIP switch
Avoid mixing DIP switch configuration and (software) parameterization.
Pos : 237 /Anleit ungen/El ektr onik /FU und St art er/4. I nbetriebnahm e/ SK 1x xE, SK 2xx E, -FD S/I nbetriebnahme G erät /Param etrier ung [SK 1x 0E, SK 2xx E] ( 2021-01-12 11:09: 58) @ 1\m od_1343219106227_14638. docx @ 37353 @ 4 @ 1
4.3.2.1
Parameterization
The use of a Parameter Box (SK CSX-3H/SK PAR) or the NORDCON- software is required in order to
adapt the parameters.
Parameter group
Parameter numbers
Functions
Comments
Basic parameters
P102 … P105
Ramp times and frequency
limits
Motor data
P201 … P207, (P208)
Data on motor nameplate
P220, function 1
Measure stator resistance
Value is written to P208
alternatively
P200
Motor data list
Selection of a 4-pole standard
NORD motor from a list
alternatively
P220, function 2
Motor identification
Complete measurement of a
connected motor
Prerequisite: Motor no more
than 3 power levels less than
the variable frequency drive
Control terminals
P400, P420
Analog and digital inputs
Pos : 238 /Anleit ungen/El ektr onik /FU und St art er/4. I nbetriebnahm e/ SK 1x xE, SK 2xx E, -FD S/I nbetriebnahme G erät /Param etrier ung _01 (INF ORMATION-W erksei nst ellung) [ SK 2xx E] @ 8\m od_1441360759202_14638.docx @ 240131 @ @ 1
Information
Factory settings
Prior to commissioning, make sure the variable frequency drive is in its factory settings (P523).
If configuration is carried out at parameter level, the DIP- switches (S1) must also be set to the 0 (OFF) position.
Pos : 239 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1