6 Operating status messages
BU 0200 en-US-4920
227
Pos : 665 /Anleit ungen/El ektr onik /FU und St art er/6. M eldung en zum Betriebsz ust and/Störm eldung en (Auflist ung)/F ehl er E007 [ SK 500P, SK 180E, SK 200E(-FDS), SK500E] @ 58\m od_1606137730820_14638. docx @ 2694962 @ @ 1
E007
7.0
Mains phase failure
Fault on supply connection side
•
A power phase is not connected
•
Line power is asymmetric
7.1
Phase failure dc-link
DC link voltage too low
•
A power phase is not connected
•
Load temporarily too high
Pos : 666 /Anleit ungen/El ektr onik /FU und St art er/6. M eldung en zum Betriebsz ust and/Störm eldung en (Auflist ung)/F ehl er E007 - Hinw eis [SK 500P, SK 200E(-FDS), SK500E] @ 58\m od_1606138157993_14638. docx @ 2695039 @ @ 1
On 7.1
Devices with external 24 V DC supply of the control
unit:
If the line voltage is switched off, but the control unit is still
supplied with 24 V DC, this error message also occurs.
If the line voltage is switched on again, the error message
must be acknowledged. It is not before until then that the
variable frequency drive can be released.
Pos : 667 /Anleit ungen/El ektr onik /FU und St art er/6. M eldung en zum Betriebsz ust and/Störm eldung en (Auflist ung)/F ehl er E008 [ SK 2xx E] @ 2\m od_1347453314366_14638.docx @ 46577 @ @ 1
E008
8.0
Parameter loss
(maximum EEPROM value
exceeded)
Error in EEPROM data
•
Software version of the stored data set not
compatible with the software version of the VFD.
NOTE:
Faulty parameters are automatically reloaded
(default data).
•
EMC interferences (see also E020)
8.1
Inverter ID error, “Inverter
type incorrect”
•
EEPROM faulty
8.2
Reserved
8.3
EEPROM KSE error
(Customer unit incorrectly
identified (customer's interface
equipment))
The upgrade level of the variable frequency drive was not
correctly identified.
EEPROM with a firmware status of version 1.2 or above
plugged in to an VFD with
older firmware status →
Loss of
parameters!
(also see
Information
in section 5)
•
Switch line voltage off and on again.
8.4
Internal EEPROM error
(Database version incorrect)
8.7
EEPROM copy differs, “EEPR
copy not the same”
Pos : 668 /Anleit ungen/El ektr onik /FU und St art er/6. M eldung en zum Betriebsz ust and/Störm eldung en (Auflist ung)/F ehl er E009 "res erviert" [ SK 180E/ SK 2x xE/ SK2x xE-FD S] @ 2\m od_1347453797027_14638. docx @ 46702 @ @ 1
E009
---
Reserved
Pos : 669 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1