5 Parameter
BU 0200 en-US-4920
157
Pos : 378 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ P3xx R egelungs par amet er [SK 2xxE] @ 1\mod_1346320887745_14638. docx @ 40078 @ 3 @ 1
5.2.4 Control parameter
In combination with an HTL incremental encoder, a closed speed control loop can be set up using
digital inputs 2 and 3 of the VFD.
Alternatively, the incremental encoder signal can also be used in another way. In order to do this,
select the required function in parameter P325.
In order to make this parameter visible, set the supervisor parameter P003 to 2 or 3.
Parameter
{factory setting}
Setting value/description/note
Device
Supervisor
Parameter
set
Pos : 379 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P300- P399/Param et er P300 – Servo Modus [ SK 2xxE, SK 2xx E-FDS, SK 5xx E] @ 0\m od_1327591436317_14638.docx @ 14939 @ @ 1
P300
Servo mode
(servo mode)
P
0 ... 2
{ 0 }
The control method for the motor is defined with this parameter. The following constraints must be
observed: In comparison with the "0" setting, the "2" setting enables somewhat higher dynamics
and control precision but it requires greater parameterization effort. In contrast, the "1" setting
operates with speed feedback from an encoder and therefore enables the highest possible quality
of speed control and dynamics.
0 =
Off (VFC open-loop)
1)
Speed control without encoder feedback
1 =
On (CFC closed-loop)
2)
Speed control with encoder feedback
2 =
Obs (CFC open-loop)
Speed control without encoder feedback
NOTE:
Commissioning information: (
Section 4.2 "Selecting the operating mode for motor control").
1)
Corresponds to the previous setting "OFF"
2)
Corresponds to the previous setting "ON"
Pos : 380 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P300- P399/Param et er P300 – Servo Modus_Ergänzung [ SK 2xxE, SK 5xx E] @ 20\mod_1513335672529_14638. docx @ 2375902 @ @ 1
Information
Operation of an IE4 motor
with (P330), setting 1 = On
(CFC closed-loop)
If an IE4 motor is operated in CFC closed-loop mode, the
slip error monitoring
must be
activated
(
P327
≠
0
).
Pos : 381 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P300- P399/Param et er P301 – Drehgeber Auflösung [ SK 2xx E(-FDS)] @ 38\m od_1568381414711_14638. docx @ 2559430 @ @ 1
P301
Incremental encoder
(encoder resolution)
0 ... 19
{ 6 }
Input of the pulse number per revolution of the connected incremental encoder.
If the encoder rotation direction is not the same as that of the VFD (depending on installation and
wiring), this can be compensated for by selecting the corresponding negative pulse numbers
8...16 or 19.