NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
192
BU 0200 en-US-4920
Pos : 498 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P512 – USS-Adres se @ 0\m od_1328092365912_14638. docx @ 15053 @ @ 1
P512
USS address
(USS address)
0 ... 30
{ 0 }
Setting of the VFD bus address for USS communication.
Pos : 499 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P513 – Tel egrammaus fallz eit [SK 1x0E, SK 2xx E, SK 2x xE-FD S] @ 2\m od_1346932166581_14638. docx @ 43124 @ @ 1
P513
Telegram time-out
(telegram timeout)
S
-0.1 / 0.0 /
0.1 ... 100.0 s
{ 0.0 }
If the variable frequency drive is directly controlled via the CAN protocol or via RS485, this
communication path can be monitored via parameter (P513). Following receipt of a valid
telegram, the next one must arrive within the set period. Otherwise the VFD reports an fault and
switches off with the error message E010 >Bus Time Out<.
The VFD monitors the system bus communication via parameter (P120). Therefore parameter
(P513) must usually be left in the factory setting {0.0}. Parameter (P513) must only be set to {-,.1}
if faults detected by the optional module (e.g. communication errors on the field bus level) are not
to result in the drive unit being switched off.
0.0
=
Off
: Monitoring is
switched off
.
-0.1
=
No error
: Even if the bus module detects an error, this does not cause the variable
frequency drive to be switched off.
0.1 …
=
On
: Monitoring is activated.
Pos : 500 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P513 – Tel egrammaus fallz eit _Ergänz ung_01 [ SK 1x0E, SK 2xxE, SK 5xx E, SK 2xx E-FDS] @ 10\m od_1456911365722_14638. docx @ 311295 @ @ 1
NOTE:
The process data channels for USS, CAN/CANopen and CANopen Broadcast are
monitoring independently of each other. The decision concerning which channel to
monitor is made by means of the setting in parameters P509 and P510.
For example, in this way it is possible to register the interruption of a CAN Broadcast
communication, although the VFD is still communicating with a Master via CAN.
Pos : 501 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P514 – CAN- Baudrat e [SK 1x0E, SK 2xx E, SK 2x xE-FD S] @ 2\m od_1346932167220_14638. docx @ 43148 @ @ 1
P514
CAN bus baud rate
(CAN bus baud rate)
S
0 ... 7
{ 5 }
Setting of the transfer rate (transfer speed) via the system bus interface. All bus participants must
have the same baud rate setting.
Note:
Optional modules (SK xU4-…) only operate with a transfer rate of 250 kBaud. Therefore the
variable frequency drive must remain at the factory setting (250 kBaud).
0 =
10 kbaud
3 =
100 kbaud
6 =
500 kbaud
1 =
20 kbaud
4 =
125 kbaud
7 =
1 Mbaud * (test purposes only)
2 =
50 kbaud
5 = 250 kbaud
*) Reliable operation cannot be guaranteed