5 Parameter
BU 0200 en-US-4920
209
Pos : 566 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ P7xx I nf ormationen @ 0\m od_1328170311705_14638. docx @ 15102 @ 3 @ 1
5.2.8 Informations
Parameter
Setting value/description/note
Supervisor
Parameter set
Pos : 567 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P700 – Ak tueller Betriebsz ust and @ 0\m od_1328170483810_14638. docx @ 15103 @ @ 1
P700
[-01]
...
[-03]
Actual operating status
(present operating status)
0.0 ... 25.4
Display of current messages for the present operating status of the variable frequency drive such
as faults, warnings or the reason why switch-on is disabled (please see chapter 6 "Operating
status messages").
[-01] = Actual fault,
shows the currently active (unacknowledged) fault(please see section "Error
[-02] = Actual warning,
indicates a current warning message (please see section "Warning
[-03] = Reason VFD blocked,
indicates the reason for an active start disable (please see section
"Notifications switch-on block, "not ready"").
NOTE
Simple Box/Control Box:
the error numbers of the warning messages and faults can be displayed
using Simple Box and Control Box.
Parameter box:
with the Parameter box the messages are displayed in plain text. In addition, the
reason for a possible disabling of starting can also be displayed.
Bus:
The display of bus-level error messages is displayed in decimal integer format. The
displayed value must be divided by 10 in order to correspond with the correct format.
Example: Display: 20 → Error number: 2.0
Pos : 568 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P701 – Letz te Stör ung 1.. .5 @ 0\m od_1328170536746_14638.docx @ 15104 @ @ 1
P701
[-01]
...
[-05]
Last fault
(Last fault 1...5)
0.0 ... 25.4
This parameter stores the last 5 faults (please see chapter 0 "Error messages").
The Simple Box/Control Box must be used to select the corresponding memory location 1...5-
(array parameter), and confirmed using the OK/ENTER key to read the stored error code.
Pos : 569 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P702 – Frequenz l etzt e St örung 1.. .5 @ 0\m od_1328170589463_14638. docx @ 15105 @ @ 1
P702
[-01]
...
[-05]
Frequency last error
(last frequency fault 1...5)
S
-400.0 ... 400.0 Hz
This parameter stores the output frequency that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.
The Simple Box/Control Box must be used to select the corresponding memory location 1...5-
(array parameter), and confirmed using the OK/ENTER key to read the stored value.
Pos : 570 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1