NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
202
BU 0200 en-US-4920
Pos : 540 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P543 – Bus-Is twert 1- 3 [ SK 1x0E, SK 2xxE, SK 2xx E-FDS] @ 2\mod_1346932171510_14638. doc x @ 43316 @ @ 1
P543
[-01]
...
[-03]
Bus actual value 1 ... 3
(actual bus value 1 ... 3)
S
P
0 ... 57
{ [-01] = 1 }
{ [-02] = 4 }
{ [-03] = 9 }
The return status value can be selected for bus actuation in this parameter.
NOTE:
For further details, please refer to the relevant bus manual or the description for
(P418). (Values from 0% … 100% correspond to 0000hex … 4000hex)
For standardization of the actual values: (please see chapter 8.9 "Standardization of
setpoint/target values").
[-01] = bus actual value 1
[-02] = bus actual value 2
[-03] = bus actual value 3
(Definition of frequencies (chapter 8.10))
Pos : 541 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P543 – Bus-Is twert 1- 3_Einst ellung en [ SK 2xx E] @ 9\m od_1448353878755_14638.docx @ 266102 @ @ 1
0 =
Off
19 =
Frequency
Master Value (P503)
1 =
Actual frequency
20 =
Set frequency After Ramp,
"Setpoint frequency after master value ramp"
2 =
Actual speed
3 =
Current
21 =
Actual freq. without slip
"Actual frequency without master value slip"
4 =
Torque current (100% = P112)
5 =
State digital-IO
22 =
Speed encoder,
"Speed from encoder"
6 =
… 7 reserved, Posicon
8 =
Setpoint frequency
23 =
Actual frequency with slip
(from software version V1.3)
"Actual frequency with slip"
9 =
Error code
10 =
… 11 reserved, Posicon
24 =
Lead actual freq.
w. slip
(SW 1.3 and above)
"Master value, actual freq. with slip"
12 =
BusIO Out Bits 0-7
13 =
… 16 reserved, Posicon
53 =
Actual value 1 PLC
17 =
Value analog input 1,
SK2x0E:
Analog input 1 (P400[-01]),
SK2x5E:
AIN1 of the first I/O
extension SK xU4-IOE (P400 [-03]))
54 =
Actual value 2 PLC
55 =
Actual value 3 PLC
56 =
Actual value 4 PLC
18 =
Value analog input 2,
SK2x0E:
Analog input 2 (P400[-02]),
SK2x5E:
AIN2 of the first I/O
extension SK xU4-IOE (P400 [-04]))
57 =
Actual value 5 PLC
* assignment of the digital inputs for P543 = 5
Bit 0 = DigIn 1 (VFD)
Bit 1 = DigIn 2 (VFD)
Bit 2 = DigIn 3 (VFD)
Bit 3 = DigIn 4 (VFD)
Bit 4 = PTC thermistor input (VFD)
Bit 5 = reserved
Bit 6 = DigOut 3 (DO1, 1st SK…IOE)
Bit 7 = DigOut 4 (DO2, 1st SK…IOE)
Bit 8 = DigIn 5 (DI1, 1st SK…IOE)
Bit 9 = DigIn 6 (DI2, 1st SK…IOE)
Bit 10 = DigIn 7 (DI3, 1st SK…IOE)
Bit 11 = DigIn 8 (DI4, 1st SK…IOE)
Bit 12 = DigOut 1 (VFD)
Bit 13 = mech. brake (VFD)
Bit 14 = DigOut 2 (VFD) (SK 2x0E)
Bit 15 = reserved
Pos : 542 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1