NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
110
BU 0200 en-US-4920
Pos : 244 /Anleit ungen/El ektr onik /FU und St art er/4. I nbetriebnahm e/ SK 1x xE, SK 2xx E, -FD S/I nbetriebnahme G erät /Pot entiom et ern P1 und P2 (SK 2x0E BG 4 und SK 2x 5E) [SK 2xxE] @ 1\mod_1343222441209_14638. docx @ 37550 @ 4 @ 1
4.3.2.4
Potentiometers P1 and P2 (SK 2x0E size 4 and SK 2x5E)
The setpoint can be set to a fixed value with integrated potentiometer P1. Adjustment of startup and
braking ramps can be made via potentiometer P2.
Potentiometers
P2
P1
Potentiometers
P1
(continuous)
P2
(stepped)
0%
P102/103
P105
-
-
-
10%
0.2 s
10 Hz
1
P102/103
P104
20%
0.3 s
20 Hz
2
0.2 s
2 Hz
30%
0.5 s
30 Hz
3
0.3 s
5 Hz
40%
0.7 s
40 Hz
4
0.5 s
10 Hz
50%
1.0 s
50 Hz
5
0.7 s
15 Hz
60%
2.0 s
60 Hz
6
1.0 s
20 Hz
70%
3.0 s
70 Hz
7
2.0 s
25 Hz
80%
5.0 s
80 Hz
8
3.0 s
30 Hz
90%
7.0 s
90 Hz
9
5.0 s
35 Hz
100%
10.0 s
100 Hz
10
7.0 s
40 Hz
The function of P1 and P2 depends on DIP 4/5. The meaning changes according to the setting.
By default, P1 sets the setpoint value of 0%-100% and P2 sets the ramp from 0.2-7 s.