5 Parameter
BU 0200 en-US-4920
191
Pos : 493 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P509 – Q uell e St euerwort [ SK 1x 0E, SK 2xx E] @ 2\m od_1346932164693_14638.docx @ 43052 @ @ 1
P509
Source Control Word
(Control word source)
S
0 ... 4
{ 0 }
Selection of the interface through which the VFD is controlled.
0 =
Contr.term. or
keyb.,
"Control terminals or keyboard control"
**
with the Simple Box (if
P510=0), the Parameter Box or via BUS I/O Bits.
1 =
Contr. Terminal only *
, the VFD can only be controlled via the digital and analog inputs or
via the bus I/O Bits.
2 =
USS*
, the control signals (enable, rotation direction, etc.) are transferred via the RS485
interface, and the setpoint is transferred via the analog input or the fixed frequencies.
3 =
Systembus *
, setting for control by master via a bus interface
4 =
Systembus broadcast *
, setting for actuation by a master drive in Master/Slave mode
(e.g. with synchronous applications)
*)
Keyboard control (Simple Box, Parameter Box) is disabled, parameterization is still
possible.
**) If communication is interrupted during keyboard control (timeout 0.5 s),
the VFD will block without an error message.
NOTE:
For details of the optional bus systems, please refer to the relevant supplementary bus manuals.
Pos : 494 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P509 – Q uell e St euerwort - Ergänz ung [SK 2xx E] @ 9\m od_1448293499605_14638. docx @ 266001 @ @ 1
As an alternative to setting the parameter,
systembus
can also be selected with DIP switch S1:3.
Pos : 495 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P510 – Q uell e Sollw erte [ SK 1x 0E, SK 2xx E] @ 2\m od_1346932165333_14638.docx @ 43076 @ @ 1
P510
[-01]
[-02]
Source Setpoints
(setpoints source)
S
0 ... 4
{ [-01] = 0 }
{ [-02] = 0 }
Selection of the setpoint source to be parameterized:
[-01] = Source main setpoint
[-02] =
Source 2nd setpoint
Selection of the interface via which the VFD receives the setpoint.
0 = Auto:
The source of the setpoint is
automatically derived from the setting of
parameter P509.
2 = USS
, see P509
3 = Systembus
, see P509
1 = Control terminal only
, digital and
analog inputs control the frequency,
including fixed frequencies
4 = Systembus broadcast
, see P509
Pos : 496 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P511 – USS-Baudrate [ SK 1x 0E, SK 2x xE, SK 2xx-FD S] @ 2\mod_1346932165972_14638. docx @ 43100 @ @ 1
P511
USS baud rate
(USS baud rate)
S
0 ... 3
{ 3 }
Setting of the transfer rate (transfer speed) via the RS485 interface. All bus participants must
have the same baud rate setting.
0 =
4800 baud
2 =
19200 baud
1 =
9600 baud
3 =
38400 baud