5 Parameter
BU 0200 en-US-4920
153
P217
Oscillation damping
(oscillation damping)
S
P
0 ... 400 %
{ 10 }
No-load resonance vibrations can be damped with oscillation damping. Parameter 217 is a
measure of the damping capacity.
In oscillation damping the oscillation component is filtered out of the torque current by means of a
high-pass filter. This is amplified by P217 and inverted to the output frequency.
The limit for the applied value is also proportional to P217. The time constant for the high-pass filter
depends on P213. For higher values of P213 the time constant is lower.
With a value of 10% for P217, a maximum of ± 0.045 Hz is applied. With 400% in P217, this
corresponds to ± 1.8 Hz.
The function is not active in "Servo mode, P300".
Pos : 363 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P200- P299/Param et er P218 – Modulati onsgrad @ 0\m od_1327590589726_14638.docx @ 14930 @ @ 1
P218
Modulation depth
(modulation depth)
S
50 ... 110 %
{ 100 }
This setting affects the maximum possible output voltage of the VFD in relation to the line voltage.
Values <100% reduce the voltage to values below that of the line voltage if this is required for
motors. Values >100% increase the output voltage on the motor. This leads to increased harmonics
in the current and can lead to oscillations in some motors.
Normally this should be set to 100%.