5 Parameter
BU 0200 en-US-4920
213
P718
[-01]
...
[-03]
Current setpoint frequency
(present setpoint frequency)
-400.0 ... 400.0 Hz
Displays the frequency specified by the setpoint (please see chapter 8.1 "Setpoint processing").
[-01] =
present setpoint frequency from the setpoint source
[-02] =
present setpoint frequency after processing in the VFD status machine
[-03] =
present setpoint frequency after frequency ramp
Pos : 590 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1
Pos : 591 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P719 – Ak tueller Str om @ 0\mod_1328172979998_14638. doc x @ 15123 @ @ 1
P719
Actual current
(present current)
0.0 ... 999.9 A
Displays the present output current.
Pos : 592 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P720 – Ak tueller M om entstrom @ 0\m od_1328173025780_14638.docx @ 15124 @ @ 1
P720
Actual torque current
(present torque current)
-999.9 ... 999.9 A
Displays the currently calculated torque-generating output current (active current). Basis for
calculation are the motor data P201...P209.
negative values = generator,
positive values = drive
Pos : 593 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P721 – Ak tueller Fel dstr om @ 0\mod_1328173074624_14638.docx @ 15125 @ @ 1
P721
Actual field current
(present field current)
-999.9 ... 999.9 A
Displays the presently calculated field current (reactive current). Basis for calculation are the
motor data P201...P209.
Pos : 594 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P722 – Ak tuelle Spannung @ 0\mod_1328173115169_14638. doc x @ 15126 @ @ 1
P722
Current voltage
(present voltage)
0 ... 500 V
Displays the actual AC voltage supplied by the VFD output.
Pos : 595 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P723 – Ak tuelle Spannungsk omponent e U d @ 0\mod_1328173153339_14638. doc x @ 15127 @ @ 1
P723
Voltage -d
(present voltage component Ud)
S
-500 ... 500 V
Displays the present field voltage component.
Pos : 596 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P724 – Ak tuelle Spannungsk omponent e Uq @ 0\mod_1328173194227_14638. doc x @ 15128 @ @ 1
P724
Voltage -q
(present voltage component Uq)
S
-500 ... 500 V
Displays the present torque voltage component.
Pos : 597 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P725 – Ak tueller cos phi @ 0\mod_1328173237475_14638. docx @ 15129 @ @ 1
P725
Current cos phi
(present cos
j
)
0.00 ... 01:00
Displays the presently calculated cos
ϕ
of the drive.
Pos : 598 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P726 – Sc heinl eist ung @ 0\m od_1328173288066_14638. docx @ 15130 @ @ 1
P726
Apparent power
(apparent power)
0.00 ... 300.00 kVA
Displays the presently calculated apparent power. Basis for calculation are the motor data
P201...P209.
Pos : 599 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P727 – Mec hanis che Leis tung @ 0\mod_1328173332220_14638. docx @ 15131 @ @ 1
P727
Mechanical power
(mechanical power)
--99.99 ... 99.99 kW
Displays the presently calculated effective power of the motor. Basis for calculation are the motor
data P201...P209.
Pos : 600 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1
Pos : 601 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P700- P799/Param et er P728 – Netzs pannung @ 0\m od_1328173378202_14638.docx @ 15132 @ @ 1