4 Commissioning
BU 0200 en-US-4920
109
Pos : 242 /Anleit ungen/El ektr onik /FU und St art er/4. I nbetriebnahm e/ SK 1x xE, SK 2xx E, -FD S/I nbetriebnahme G erät /DIP- Sc halt er Analog eingang (nur SK 2x 0E) [ SK 2xx E] @ 1\m od_1343221317551_14638.docx @ 37526 @ 45 @ 1
4.3.2.3
DIP switches, analog input (only SK 2x0E)
The analog inputs in the SK 2x0E are suitable for current and voltage
setpoints. For correct processing of current setpoints (0-20 mA/4-20 mA)
the relevant DIP switch must be set for current signals ("ON").
Adjustment to wire-break-proof signals (2-10 V/4-20 mA) is made via
parameters (P402) and (P403).
Access to DIP switches
SK 2x0E
Access
Detail
Size 1 … 3
… from outside,
middle diagnostic
opening
Size 4
... from inside