NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
194
BU 0200 en-US-4920
Pos : 510 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P520 – Fangsc halt ung @ 0\m od_1328092790587_14638.docx @ 15061 @ @ 1
P520
Flying start
(flying start)
S
P
0 ... 4
{ 0 }
This function is required to connect the VFD to already rotating motors, e.g. in fan drives. Motor
frequencies >100 Hz are only picked up in speed controlled mode (Servo mode P300 = ON).
0 = Switched off
, no flying start.
1 = Both directions
, the VFD looks for a speed in both directions.
2 = Direction of setpoint
, searches only in the direction of the setpoint value which is present.
3 = Both dir. after fault
, same as { 3 } but only after mains failure or fault
4 = Setpoint after fault
same as { 2 } but only after mains failure or fault
NOTE:
For physical reasons, the flying start circuit only operates above 1/10 of the nominal
motor frequency (P201), however not below 10 Hz.
Example 1
Example 2
(P201)
50Hz
200Hz
f=1/10*(P201)
f=5 Hz
f=20Hz
Comparison of f vs. f
min
with:
f
min
=10 Hz
Result f
fly
=
5 Hz < 10 Hz
The flying start circuit
functions above f
fly
=10 Hz.
20 Hz > 10 Hz
The flying start circuit
functions above f
fly
=20 Hz.
Pos : 511 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P520 – Fangsc halt ung_Ergänz ung_01 [SK 2xx E, SK 5xxE, SK 2xx E-FDS] @ 10\m od_1456915162493_14638.docx @ 311480 @ @ 1
NOTE:
PMSM
: The catch function automatically determines the direction of rotation. The
device therefore behaves in an identical way to function 1 with the setting for
function 2. The device behaves in an identical way to function 3 with the setting for
function 4.
In CFC closed loop operation, the catch circuit can only be executed if the rotor
position is known in relation to the incremental encoder. For this purpose, the motor
initially cannot rotate when it is switched on for the first time after a "Power On" of
the device.
Pos : 512 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P521 – Fangsc halt ung Aufl ösung @ 0\mod_1328092909572_14638. doc x @ 15062 @ @ 1
P521
Flying start resolution
(flying start resolution)
S
P
0.02... 2.50 Hz
{ 0.05 }
Using this parameter, the flying start circuit search increment size can be adjusted. Values that
are too large affect accuracy and causes the VFD to cut out with an overcurrent message. If the
values are too small, the search time is greatly extended.
Pos : 513 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P522 – Fangsc halt ung Of fs et @ 0\m od_1328093001838_14638. docx @ 15063 @ @ 1
P522
Flying start offset
(flying start offset)
S
P
-10.0 ... 10.0 Hz
{ 0.0 }
A frequency value that can be added to the frequency value found, e.g. to remain in the motor
range and so avoid the generator range and therefore the chopper range.
Pos : 514 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1