- 122 -
[
VII
Control ]
Note1: All are set to OFF at factory shipment. Unless otherwise specified, set the switch to OFF where indicated by "-,"
which may be set to a certain setting for a reason.
Note2: Cooling-only operation is performed to prevent freezing when the water temperature TH6 reaches below 5°C[41°F]
or TH9 reaches below 3°C[37°F] while the compressor is stopped.
This operation is stopped when both TH6 and TH9 reach abode 10°C[50°F], two hours have passed since the be-
ginning of this operation, or a signal to resume normal operation is received.
SW4
1
-
-
-
-
2
-
-
-
-
3
-
-
-
-
4
-
-
-
-
5
-
-
-
-
6
-
-
-
-
7
NIGHT MODE/Step
DEMAND mode
NIGHT MODE
Step DEMAND
Before power on
8
-
-
-
-
9
-
-
-
-
10
-
-
-
-
SW5
1
-
-
-
-
2
-
-
-
-
3
LED Display
"°C" "kg/cm
2
G"
"°F" "psi"
When switching on the power
4
-
-
-
-
5
-
-
-
-
6
-
-
-
-
7
-
-
-
-
8
-
-
-
-
9
-
-
-
-
10
-
-
-
-
Switch
Function
Function according to switch setting
Switch setting timing
OFF
ON
OFF
ON