- 137 -
[
VII
Control ]
-11- Method of Cooling the Control Box <PQHY/PQRY>
The control box of the PQHY/PQRY models of units is equipped with a refrigerant evaporator to cool the heat that is gen-
erated within the control box.
It supplies refrigerant to the evaporator during inverter operation and also cools the inside of the unit and the control box
by operating the cooling fan inside the control box.
(1) Cooling fan control
1) If the heatsink fin temperature exceeds 80°C [176°F], cooling fan comes on and stays on until the temperature goes
below 80°C [176°F]. During this time, inverter startup is prohibited.
2) While the inverter is in operation, the fan always stays on.
3) Once the cooling fan comes on, it stays on for at least five minutes.
(2) LEV2 control
1) LEV2 control range
0 LEV2 100 pulses
2) LEV2 control method
Refer to the table below.
[During cooling only or cooling main operation]
SHB=THINV-Te(Evaporating
temperature)
THHS
LEV2
6°C[11°F]
SHB
55°C[131°F]
THHS
Up
THHS < 55°C[131°F]
Down
SHB < 6°C[11°F]
55°C[131°F]
THHS
Down
THHS < 55°C[131°F]
Down
-
-
Down
[During heating only or heating main operation]
Evaporating temperature
Te
SHB=THINV-Te(Evaporating
temperature)
THHS
LEV2
9°C[48°F]
Te
-
-
Up
7°C[45°F]
Te
< 9°C[48°F]
-
-
Up
Te < 7°C[45°F]
6°C[11°F]
SHB
55°C[131°F]
THHS
Up
THHS < 55°C[131°F]
Down
SHB < 6°C[11°F]
55°C[131°F]
THHS
Down
THHS < 55°C[131°F]
Down
-
-
-
Down
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...