- 52 -
[
II
Restrictions ]
Wiring method/address setting method
Pro
ce-
du-
res
Unit or controller
Address
setting
range
Setting method
Notes
Facto-
ry set-
ting
2
Opera-
tion with
the
M-NET
remote
control-
ler
Indoor
unit
Main
unit
IC
01 to 50
After assigning an address to all
indoor units to be controlled
from the MA remote controller,
assign the smallest address to
the main indoor unit in the
group.
In an R2 or WR2 system with a
sub BC controller, make the
settings for the indoor units in
the following order.
(i) Indoor unit to be connected
to the main BC controller
(ii) Indoor unit to be connected
to sub BC controller 1
(iii) Indoor unit to be connected
to sub BC controller 2
Make the settings for the indoor
units in the way that the formula
"(i) < (ii) < (iii)" is true.
Enter the indoor unit
group settings on the
system controller
(MELANS).
Port number setting is
required by an R2 or
WR2 system.
00
Sub
unit
Assign sequential numbers start-
ing with the address of the main
unit in the same group +1. (Main
unit a1, main unit ad-
dress +2, main unit a3,
etc.)
M-NET
re-
mote
con-
troller
Main
re-
mote
con-
troller
RC
101 to 150 Add 100 to the main unit address
in the group.
It is not necessary to set
the 100s digit.
To set the address to
200, set it to 00.
101
Sub
re-
mote
con-
troller
RC
151 to 200 Add 150 to the main unit address
in the group.
3
LOSSNAY
LC
01 to 50
Assign an arbitrary but unique ad-
dress to each of these units after
assigning an address to all indoor
units.
None of these addresses
may overlap any of the in-
door unit addresses.
00
4
Outdoor (heat source) unit
OC 51 to 100
The sum of the smallest address
of the indoor units in the same
system and 50
To set the address to 100,
set it to 50.
00
5
Auxilia-
ry unit
BC controller
(main)
BC
52 to 100
Outdoor (heat source) unit ad-
dress + 1
To set the address to
100, set it to 50.
If a given address over-
laps any of the address-
es that are assigned to
the outdoor (heat
source) units or to the
sub BC controller, use a
different, unused ad-
dress within the setting
range.
The use of a sub BC
controller requires the
connection of a main
BC controller.
00
BC controller
(sub)
BS
Assign an address that equals the
sum of the smallest address of
the indoor units that are connect-
ed to the sub BC controller and
50.
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...