- 58 -
[
II
Restrictions ]
(2) Line branching
System that requires more than 16 BC controller ports or with multiple BC controllers
<System with both main and sub BC controllers>
* A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub), and
three pipes will be used between the main and the sub BC controllers.
* In the system to which indoor units of P72 model or above are connected, neither a branch joint nor a branch header
may be used.
Unit: m [ft]
Operation
Pipe sections
Allowable length of pipes
Length
Total pipe length
A+B+C
+a+b+c+d+e+f+g
300 [984] or less
*1
*1. When the aggregate length of all pipes exceeds 300m [984ft], observe the restrictions in the figure titled "Restrictions
on pipe length" below.
Total pipe length from the heat source unit to the
farthest indoor unit
A+C+g or C+g
150 [492] or less
(Equivalent length 175 [574] or less)
Between heat source unit and BC controller
A
110 [360] or less
Between BC controller and indoor unit
e or C+g
40 [131] or less
*2
*2. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131ft], observe the
restrictions in the figure titled "Restrictions on pipe length" below. (Except the P96 models)
Height
difference
Between indoor and
heat source units
Heat source unit above
indoor unit
H
50 [164] or less
Heat source unit below
indoor unit
H'
40 [131] or less
Between indoor unit and BC controller
h1
15 [49] or less (10 [32] or less)
*3
*3. When the capacity of the connected indoor units is P72 or above, use the figures in the parentheses as a reference.
Between indoor units
h2
15 [49] or less (10 [32] or less)
*3
Between main BC controller and sub BC controller
h3
15 [49] or less
Between indoor unit (main BC controller) and
indoor unit (sub BC controller)
h4
15 [49] or less (10 [32] or less)
*3*4
*4. When connecting 2 sub BC controllers to a system, observe the allowable length in the table above.
Heat source unit
B
A
a
b
c
C
f
g
h3
h4
d
e
H=50 m [164ft] or less(Heat source unit above indoor unit)
H'=40 m [131ft] or less(Heat source unit below indoor unit)
h1=15m [49ft] or less
h2=15m [49ft] or less
110 m [360ft] or less
40 m [131ft] or less
BC controller
main unit
BC controller
sub unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
<System that requires more than 16 BC controller ports>
Indoor unit
Indoor unit
Note1) When connecting 2 sub BC controllers to a system, install them in parallel.
Note1)
(P161 - P280 models:
2 ports merged with
a junction pipe)
Junction pipe
(Optional accessory)
Branch joint
(For use with the Y series)
CMY-Y102S-G
Maximum of 3 units per port
Total capacity of P160 or below
(All units connected to the same port
must be in the same operating mode)
Restrictions on pipe length
The height difference and the pipe length between BC controller and indoor units (A)
Height difference between main BC controller and farthest indoor unit (m[ft])
Aggregate length of all pipes (m[ft])
Pipe length between main BC
controller and farthest indoor unit (m[ft])
400[1312]
350[1148]
300[984]
250[820]
200[656]
30
[98]
40
[131]
50
[164]
60
[196]
70
[229]
80
[262]
90
[295]
100
[328]
110
[360]
Pipe length between heat source unit and BC controller (m[ft])
70[229]
60[196]
40[131]
30[98]
50[164]
10[32]
20[65]
0 0
5
[16]
10
[32]
15
[49]
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...