Troubleshooting ]
(3) Check method and remedy
1) Measures against noise
Check the followings when noise exists on the wave or the errors described in (1) occur.
Error code definition
Remedy
Check
that the
wiring
work is
per-
formed
accord-
ing to wir-
ing
specifica-
tions.
1.The transmission line and the power
208 / 230 V line are not wired too
closely.
Isolate the transmission line from the power line (5cm [1-31/
32"] or more). Do not insert them in the same Do not insert
them in the same conduit.
2.The transmission line is not bundled
with that for another systems.
The transmission line must be isolated from another transmis-
sion line.
When they are bundled, erroneous operation may be caused.
3.The specified wire is used for the
transmission line.
Use the specified transmission line.
Type: Shielded wire CVVS/CPEVS/MVVS (For M-NET re-
mote controller)
Diameter: 1.25mm
2
[AGW16] or more
(Remote controller wire: 0.3 - 1.25mm
2
[AGW22-16])
4.When the transmission line is daisy-
chained on the indoor unit terminals,
are the shields daisy-chained on the
terminals, too?
The transmission is two-wire daisy-chained. The shielded
wire must be also daisy-chained.
When the shielded cable is not daisy-chained, the noise can-
not be reduced enough.
Check
that the
ground-
ing work
is per-
formed
accord-
ing to
ground-
ing speci-
fications.
5.Is the grounding of the shield of the
transmission line (for indoor unit con-
trol) provided on the indoor unit?
One point grounding must be provided on the heat source
unit. If no grounding is provided, the noise on the transmission
line cannot escape leading to change of the transmission sig-
nal.
6.Check the treatment method of the
shield of the transmission line (for cen-
tralized control).
When group operation of indoor units connected to different
heat source units is performed, provide grounding of the
shield of the transmission line for centralized control at the
point of heat source unit, and when the system controller is
used, provide grounding at the point of the system controller,
so that the effect of noise can be minimized.
The environment against noise varies depending on the dis-
tance of the transmission lines, the number of the connected
units, the type of the controllers to be connected, or the envi-
ronment of the installation site. Therefore, the transmission
line work for centralized control must be performed as follows.
(1) When no grounding is provided
Group operation of indoor units connected to different
heat source units: One point grounding on one heat
source unit (power supply unit)
Use of MELANS: Grounding on the main controller
(power supply device)
(2) When an error occurs even though one point grounding
is provided: Ground the shield on all heat source units.
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...