- 21 -
[
II
Restrictions ]
(6) Various start-stop controls (Indoor unit settings)
Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10.
(7) Miscellaneous settings
Cooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 "OFF.")
When using indoor unit as a cooling-only unit, set SW3-1 to ON.
(8) Various types of control using input-output signal connector on the outdoor (heat source) unit (various connection op-
tions)
Function
Operation of the indoor unit when the operation is
resumed after the unit was stopped
Setting (SW1)
*1
*1. Requires that the dipswitch settings for all the units in the group be made.
9
10
Power ON/OFF by the plug
*2*3*4
*2. Not applicable to units with a built-in drain pump or humidifier.
*3. Models with a built-in drain pump cannot be turned on/off by the plug individually. All the units in the same refrigerant
circuits will be turned on or off by the plug.
*4. Do not cut off power to the outdoor (heat source) unit. Cutting off the power supply to the outdoor (heat source) unit
will cut off the power supply to the crankcase heater and may cause the compressor to malfunction when the unit is
put back into operation.
Indoor unit will go into operation regardless of its oper-
ation status before power off (power failure). (In ap-
prox. 5 minutes)
OFF
ON
Automatic restoration after power failure
Indoor unit will go into operation if it was in operation
when the power was turned off (or cut off due to power
failure). (In approx. 5 minutes)
ON
OFF
Indoor unit will remain stopped regardless of its opera-
tion status before power off (power failure).
OFF
OFF
Type
Usage
Function
Terminal
to be
used
Input
Prohibiting cooling/heating operation (thermo OFF) by an external input to
the outdoor (heat source) unit.
*It can be used as the DEMAND control device for each system.
Compressor
ON/OFF (level)
CN3D
Performs a low level noise operation of the outdoor (heat source) unit by
an external input to the outdoor (heat source) unit.
(The unit can perform a NIGHT MODE operation under the following con-
ditions: Outdoor air temperature below 30°C during cooling operation/Out-
door air temperature above 3°C during heating operation.)
NIGHT MODE or
STEP DEMAND
(level)
*1
*1. NIGHT MODE is valid when Dip SW4-7 on the outdoor (heat source) unit are set to OFF. When Dip SW4-7 are set
to ON, STEP DEMAND control is possible, using different configurations of NIGHT MODE input and compressor ON/
OFF input settings.
Forces the outdoor (heat source) unit to perform a fan operation by receiv-
ing signals from the snow sensor.
Snow sensor signal
input (level)
CN3S
Output
How to extract signals from the outdoor (heat source) unit
*It can be used as an operation status display device.
*It can be used for an interlock operation with external devices.
Operation status of
the compressor
CN51
Error status
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...