- 208 -
[
IX
Troubleshooting ]
(3) System connected to the system controllers (MELANS)
Error Code
Error definition and error detection method
6607
(Contin-
ued)
No ACK abnormality
The error is detected when no acknowledgement (ACK signal) is received after the
transmission. (eg. When the data is transmitted six times in a row with 30 seconds
interval, the error is detected on the transmission side.)
Note: The address/attribute appeared on the display on the remote controller
indicates the controller which did not provide the response (ACK).
Error
source ad-
dress
Error dis-
play
Detection
method
Cause
Check method and remedy
M-NET re-
mote con-
troller (RC)
M-NET re-
mote con-
troller (RC)
System
controller
(SC)
MA remote
controller
(MA)
No ac-
knowl-
edgement
(ACK) at IC
transmis-
sion to RC
Same as grouping of units in a sys-
tem with multiple heat source units
Same remedy as that for grouping of units
in a system with multiple heat source units
system
controller
(SC)
No ac-
knowl-
edgement
(ACK) at
MELANS
transmis-
sion to RC
1. Error occurrence on some IC
(1) Same cause as that for system
with one heat source unit
Same remedy as that for system with
one heat source unit
2. Error occurrence on all IC in the
system with one heat source unit
(1) An error is found by the heat
source unit.
Total capacity error (7100)
Capacity code error (7101)
Error in the number of connect-
ed units (7102)
Address setting error (7105)
(2) Disconnection or short circuit of
the transmission line for the heat
source unit on the terminal block
for centralized control line con-
nection (TB7)
(3) Turn off the power source of the
heat source unit
(4) Malfunction of electrical system
for the heat source unit
1) Check the LED display for troubleshoot-
ing on the heat source unit.
-> If an error is found, check the check
code definition, and correct the error.
-> If no error is found, check the cause
2).
2) Check (2) - (4) on the left.
3. Error occurrence on all IC
(1) Same causes as (1) - (4) de-
scribed in 2.
(2) When the power supply unit for
transmission lines is used and
the male power supply connec-
tor is connected to the female
power supply switch connector
(CN40) for the transmission line
for centralized control
(3) Disconnection or shutdown of
the power source of the power
supply unit for transmission line
(4) System controller (MELANS)
malfunction
Check (1) - (4) on the left.
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...