Troubleshooting ]
High pressure sensor failure (BC controller)
Error Code
Error definition and error
detection method
Cause
Check method and remedy
5201
Liquid side
When the pressure of
4.06MPa [589psi] or more
is detected by the pressure
sensor, an error code
"5201" or "5203" will be
displayed.However, an er-
ror stop is not made, and
backup operation will be
started by other sensors.
(1) High pressure sensor fail-
ure
Refer to the page on the troubleshooting of
the high pressure sensor.(9.[4].-1-)
5203
Intermediate
(2) Inner pressure drop due to a
leakage.
(3) Torn wire coating
(4) A pin on the male connector is
missing or contact failure
(5) Disconnected wire
(6) High pressure sensor input cir-
cuit failure on the main board