4220
Logic error
(Detail code
No.111)
If only the H/W error logic
circuit operates, and no
identifiable error is de-
tected.
(1) External noise
(2) Compressor INV board
failure
(3) G/A board failure
(4) IPM failure
(5) DCCT failure
Refer to 9 [4] -7- (2) [1]
Replace the G/A board.
Refer to 9 [4] -7- (2) [5]
Replace DCCT.
4230
Heatsink over-
heat protection
When the heat sink tem-
perature(THH S1) 95°C
[203°F] or higher is de-
tected.
(1) Cooling fan malfunction
Check for disconnected connectors
and broken wires.
Check the resistance of the cooling
fan.
Resistance of the cooling fan: Sever-
al hundred ohm -1k ohm
(2) LEV2 failure
Refer to the section "Troubleshoot-
ing the LEV."
(3) THINV failure
Check for a disconnected thermistor
or broken wire.
Check sensor resistance.
Refer to 6. [2].1.
(4) THHS failure
(5) Blocked air pathway
Check for a clogged air passage.
(6) Compressor INV board
cooling fan output failure
Confirm that a voltage of 208/230V
is applied to the compressor INV
board connector CNFAN during in-
verter operation.
(7) Power supply
Check the supply voltage.
Make sure that the supply voltage
between the phases is equal to or
greater than 187V.
(8) IPM failure
Refer to 9.[4].-7-.(2).[2]
Check for the ground faulting of the
compressor or winding wire prob-
lem.
Refer to 9.[4].-7-.(2).[5]
Check the inverter circuit.
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...