- 40 -
[
II
Restrictions ]
Address setting method
Pro
ce-
du-
res
Unit or controller
Address
setting
range
Setting method
Notes
Facto-
ry set-
ting
1
Indoor
unit
Main unit
IC
01 to 50
Assign the smallest address to
the main unit in the group.
In an R2 or WR2 system with a
sub BC controller, make the set-
tings for the indoor units in the fol-
lowing order.
(i) Indoor unit to be connected to
the main BC controller
(ii) Indoor unit to be connected to
sub BC controller 1
(iii) Indoor unit to be connected to
sub BC controller 2
Make the settings for the indoor
units in the way that the formula
"(i) < (ii) < (iii)" is true.
Port number setting is re-
quired by an R2 or WR2
system.
00
Sub unit
Assign sequential numbers starting
with the address of the main unit in
the same group +1. (Main unit ad-
dress +1, main unit a2,
main unit a3, etc.)
2
LOSSNAY
LC
01 to 50
Assign an arbitrary but unique ad-
dress to each of these units after
assigning an address to all indoor
units.
None of these addresses
may overlap any of the in-
door unit addresses.
00
3
MA
remote
control-
ler
Main
remote
controller
MA
No
settings
required.
-
Enter the same indoor
unit group settings on the
system controller as the
ones that were entered
on the MA remote con-
troller.
Main
Sub
remote
controller
MA
Sub
remote
controller
Settings to be made according to
the remote controller function se-
lection
4
Outdoor (heat
source) unit
OC
51 to 100 The sum of the smallest address of
the indoor units in the same system
and 50
To set the address to
100, set it to 50.
00
5
Auxiliary
unit
BC
controller
(main)
BC
52 to 100 Outdoor (heat source) unit address
+ 1
To set the address to
100, set it to 50.
If address that is as-
signed to the main BC
controller overlaps any
of the addresses that
are assigned to the out-
door (heat source)
units or to the sub BC
controller, use a differ-
ent, unused address
within the setting
range.
The use of a sub BC
controller requires the
connection of a main
BC controller.
00
BC
controller
(sub)
BS
51 to 100 Assign an address that equals the
sum of the smallest address of the
indoor units that are connected to
the sub BC controller and 50.
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...