- 210 -
[
IX
Troubleshooting ]
(4) Errors that are not limited to a particular system
Error Code
Error definition and error detection method
6607
(Contin-
ued)
No ACK abnormality
The error is detected when no acknowledgement (ACK signal) is received after the
transmission. (eg. When the data is transmitted six times in a row with 30 seconds
interval, the error is detected on the transmission side.)
Note: The address/attribute appeared on the display on the remote controller
indicates the controller which did not provide the response (ACK).
Error
source ad-
dress
Error dis-
play
Detection
method
Cause
Check method and remedy
Address
which
should not
be existed
-
-
(1) Although the address of M-NET
remote controller has been
changed after the group is set
using M-NET remote controller,
the indoor unit is keeping the
memory of the previous ad-
dress.The same symptom will
appear for the registration with
SC.
(2) Although the address of LOSS-
NAY has been changed after the
interlock registration of LOSS-
NAY is made using M-NET re-
mote controller, the indoor unit is
keeping the memory of the pre-
vious address.
Delete unnecessary information of non-ex-
isting address which some indoor units
have.
Use either of the following two methods for
deletion.
1) Address deletion by M-NET remote
controller
Delete unnecessary address informa-
tion using the manual setting function of
M-NET remote controller. Refer to this
service handbook "4. [2]. Group set-
tings and interlock settings via the ME
remote controller 1. (3) Address dele-
tion".
2) Deletion of connection information of
the heat source unit by the deleting
switch
Note that this switch deletes all the
group information set via M-NET re-
mote controller and all the interlock
information of LOSSNAY and the in-
door unit.
Turn off the power source of the heat
source unit, and wait for 5 minutes.
Turn on the dip switch (SW2-2) on the
heat source unit main board.
Turn on the power source of the heat
source unit, and wait for 5 minutes.
Turn off the power source of the heat
source unit, and wait for 5 minutes.
Turn off the dip switch (SW2-2) on the
heat source unit main board.
Turn on the power source of the heat
source unit.
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...