- 111 -
[
VI
Refrigerant Circuit ]
Linear ex-
pansion
valve
(LEV)
LEV1
(SC coil)
Adjusts the amount of bypass
flow from the liquid pipe on the
heat source unit during cooling
DC12V
Opening of a valve driven by a
stepping motor 0-480 pulses
(direct driven type)
Same with
indoor LEV
The resis-
tance val-
ue differs
from that
of the in-
door LEV.
(Refer to
the page of
LEV trou-
bleshoot-
ing.)
LEV2
Controls refrigerant flow of the in-
verter cooling heat exchanger
Heater
CH11
Crankcase
heater
Heats the refrigerant in the com-
pressor
Cord heater
AC208/230V
CH11:
928ohm 57W (230V)
Resis-
tance
check
4-way
valve
21S4a
Changeover between heating
and cooling
AC208/230V
Dead: cooling cycle
Live: heating cycle
Continuity
check with
a tester
Part
name
Symbols
(functions)
Notes
Usage
Specifications
Check
method
Summary of Contents for City Multi CMB-P1016NU-G