- 258 -
[
IX
Troubleshooting ]
Phenomena
Cause
3
"HO" or "PLEASE WAIT" dis-
play on the remote controller
does not disappear, and no op-
eration is performed even if the
button is pressed.
Without using MELANS
1. Heat source unit address is set to "00"
2. A wrong address is set.
A wrong address is set to the indoor unit to be coupled with the remote controller.
100 must be subtracted from the address of the M-NET remote controller.
A wrong address is set to the M-NET remote controller
(100 must be added to the address of the indoor unit.)
3. Faulty wiring of the terminal block for transmission line (TB5) of the indoor unit in the same group
with the remote controller.
4. The centralized control switch (SW2-1) on the heat source unit is set to ON.
5. Disconnection or faulty wiring of indoor unit transmission line.
6. Disconnection between the terminal block for M-NET line connection (TB5) of the indoor unit and
the male connector (CN2M)
7. The male power supply connectors on 2 or more heat source units are connected to the female
power supply switch connector (CN40) for the transmission line for centralized control.
8. Heat source unit main board failure
9. Indoor unit board failure
10.Remote controller failure
Interlocking control with MELANS
11.No group registration is made using MELANS. (The indoor unit and the M-NET remote controller
are not grouped.)
12.Disconnected transmission line for centralized control (TB7) of the heat source unit
13.In the system to which the power supply unit for transmission lines is connected, the male power
supply connector is connected to the female power supply switch connector (CN40) on the heat
source unit
Check method and remedy
Using MELANS
When MELANS is used, "HO" or "PLEASE WAIT" display on the remote controller will disappear when the indoor unit and the local
remote controller (M-NET remote controller) are grouped.
If "HO" or "PLEASE WAIT" does not disappear after the registration, check the 11. - 13.
YES
YES
YES
YES
YES
YES
YES
NO
NO
*1
*1. When the heat source unit address is set to 1 - 50, the address will be forcibly set to 100.
NO
NO
NO
NO
NO
Without using MELANS
Are all the units in the system
experiencing the same problem?
Check the address of
the heat source unit.
51 - 100?
Check the centralized centralized
switch (SW2-1) on the heat source unit.
ON?
Heat source unit main
board failure
A wrong address is set
to the heat source unit.
Wrong switch setting
Change it from
ON to OFF.
A wrong address is
set to the M-NET
remote controller.
A wrong address is
set to the indoor unit.
Wrong wiring of the
M-NET transmission
line of the indoor unit
Disconnected
connector (CN2M)
Correct
the error.
Disconnected?
17 - 30V?
M-NET remote controller
- 100?
Check the address of the
indoor unit to be coupled.
Indoor unit + 100?
Check the address of the M-NET remote
controller on which "HO" is displayed.
Check connection between indoor M-NET
transmission terminal block (TB5) and the
male connector (CN2M)
Measure voltages of the terminal
block for transmission line (TB5)
on the indoor unit.
Indoor unit board or
remote controller failure
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...