- 56 -
[
II
Restrictions ]
(3) A combination of line and header branching
Unit: m [ft]
Operation
Pipe sections
Allowable length of
pipes
Length
Total pipe length
A+B+C
+a+b+c+d+e
300 [984] or less
Total pipe length (L) from the heat source unit to
the farthest indoor unit
A+B+b
150 [492] or less
Total pipe length from the first branch to the far-
thest indoor unit ( )
B+b
40 [131] or less
Height
difference
Between indoor and
heat source units
Heat source unit above
indoor unit
H
50 [164] or less
Heat source unit below
indoor unit
H'
40 [131] or less
Between indoor units
h
15 [49] or less
L
H
H'
A
A
B
C
a
b
c
d
h
e
First branch
(Branch joint)
5
1
2
3
4
Note : "Total sum of downstream unit model numbers"
in the table is the sum of the model numbers
of the units after point A in the figure.
Branch joint
Branch header
cap
Indoor
Indoor
Indoor
Indoor
Indoor
To downstream units
Note : Pipes from the header may not be
re-branched.
Heat source unit
Summary of Contents for City Multi CMB-P1016NU-G
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 38: ... 29 II Restrictions ...
Page 42: ... 33 II Restrictions ...
Page 46: ... 37 II Restrictions ...
Page 50: ... 41 II Restrictions ...
Page 54: ... 45 II Restrictions ...
Page 58: ... 49 II Restrictions ...
Page 75: ... 66 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 111: ... 102 ...
Page 113: ... 104 ...
Page 129: ... 120 ...
Page 163: ... 154 ...
Page 165: ... 156 ...
Page 187: ... 178 ...
Page 313: ... 304 ...